Használati útmutató Elco THISION L
Elco
Fűtési kazán
THISION L
Olvassa el alább 📖 a magyar nyelvű használati útmutatót Elco THISION L (164 oldal) a Fűtési kazán kategóriában. Ezt az útmutatót 8 ember találta hasznosnak és 2 felhasználó értékelte átlagosan 4.5 csillagra
Oldal 1/164

THISION L
Operation and Installation manual
for authorized technicians only
Betriebsanleitung
für die autorisierte Fachkraft
Bedienings- en Installatiehandleiding
alleen voor bevoegde vakmensen
Notice d’installation et d’emploi
réservée à l’usage des techniciens agréés
Istruzioni per l'uso
solo per il tecnico autorizzato
08/2012 DOC3078 / 12103187


Operation and Installation manual
for authorized technicians only
THISION L
08/2012 DOC3078 / 12103187

Contents
2
Contents .................................................................. 2
Safety General regulations ................................... 3
Application ................................................. 3
Norms and regulations .............................. 3
Construction Layout of boiler .......................................... 4
Operating principle .................................... 4
Technical data .................................................................. 5
Extent of delivery Standard boiler .......................................... 7
Accessories ............................................... 7
Installation Boiler transport .......................................... 8
Removing the casing ................................. 8
Boiler installation ....................................... 9
Connecting the boiler ................................ 9
Wiring diagram - Boiler .............................. 11
Wiring diagram - Accessories .................... 12
Commissioning Water and hydraulic system ...................... 13
Gas supply ................................................ 14
Condensate connection ............................. 14
Flue and air intake connections ................. 14
Prepare boiler for first startup .................... 15
Combustion analysis ................................. 16
Check water flow ...................................... 17
Check functionality of safety devices ........ 18
Gas tightness check .................................. 18
Boiler shut down ........................................ 18
Commissioning protocol ............................ 19
Operating instructions Controls .................................................... 20
Display / Programming .............................. 21
Overview of main functions ....................... 22
Maintenance Checklist .................................................... 23
Replacing the electrodes ........................... 23
Cleaning the condensate receptacle ......... 24
Cleaning and refilling the syphon .............. 24
Inspection of combustion chamber ............ 24
Water pressure and quality ....................... 25
Water flow rate .......................................... 25
Combustion analysis ................................. 25
Gas pressure ............................................. 25
Gas tightness check .................................. 25
Safety devices ........................................... 25
Maintenance protocol ................................ 26
Lockouts .................................................................. 27
Sensor values .................................................................. 30
Declaration of Conformity .................................................................. 31

Safety
General regulations
Application
Norms and regulations
3
General regulations
This documentation contains important
information, which is a base for safe
and reliable installation, commissioning
and operation of the THISION L boiler.
All activities described in this document
may only be excecuted by authorized
companies.
Changes to this document may be ef-
fected without prior notice. We accept
no obligation to adapt previously deliv-
ered products to incorporate such
changes.
Only original spare parts may be used
when replacing components on the
boiler, otherwise warranty will be void.
Application
The THISION L boiler may be used for
heating and hot water production pur-
poses only. The boiler should be con-
nected to closed systems with a maxi-
mum temperature of 100ºC (high limit
temperature), maximum setpoint tem-
perature is 90ºC.
Norms and regulations
When installing and operating the
boiler, all applicable norms (european
and local) should be fulfilled:
Local building regulations for install-
ing combustion air and flue gas sys-
tems;
Regulation for connecting the boiler to
the electrical appliance;
Regulations for connecting the boiler
to the local gas network;
Norms and regulations according to
safety equipment for heating systems;
Any additional local laws/regulations
with regard to installing and operating
heating systems.
Additional national standards
Germany:
RAL - UZ 61 / DIN 4702-8
Switzerland:
SVGW
Vorschriften der kantonalen Instanzen
(z.B. Feuerpoilizeivorschriften)
Netherlands:
GASKEUR BASIS
GASKEUR SV
GASKEUR HR107
Belgium:
HR TOP
The THISION L boiler is CE approved
and applies to the following Euro-
pean standards:
92 / 42 / EEC
Boiler efficiency directive
2009 / 142 / EEC
Gas appliance directive
2006 / 95 / EEC
Low voltage directive
2004 / 108 / EEC
EMC directive
EN 483
Gas-fired central heating boilers -
Type C boilers of nominal heat input
not exceeding 70 kW
EN 15420
Gas-fired central heating boilers -
Type C boilers of nominal heat input
exceeding 70 kW, but not exceeding
1000 kW
EN 15417
Gas-fired central heating boilers -
Specific requirements for condensing
boilers with a nominal heat input
greater than 70 kW but not exceeding
1000 kW
EN 50165
Electrical equipment of non-electric
appliances for household and similar
purposes - Safety requirements
EN 15502-1
Gas-fired central heating boilers -
Part 1: General requirements and
tests
EN 55014-1 (2000)
Electromagnetic compatibility - Re-
quirements for household appliances,
electric tools and similar apparatus -
Part 1: Emission
EN 55014-2 (1997)
Electromagnetic compatibility - Re-
quirements for household appliances,
electric tools and similar apparatus -
Part 2: Immunity - Product family
standard
EN 61000-3-2 (2000)
Electromagnetic compatibility (EMC) -
Part 3-2: Limits - Limits for harmonic
current emissions (equipment input
current 16 A per phase)
EN 61000-3-3 (2001)
Electromagnetic compatibility (EMC) -
Part 3-3: Limitation of voltage
changes, voltage fluctuations and
flicker in public low-voltage supply
systems, for equipment with rated
current 16 A per phase and not sub-
ject to conditional connection
EN 60335-1 (2002)
Household and similar electrical appli-
ances - Safety - Part 1: General re-
quirements
EN 60335-2-102 (2006)
Household an similar electrical
appliances: Particular requirements
for gas, oil and solid-fuel burning ap-
pliances having electrical connections

Construction
Layout of boiler
Operating principle
4
Layout of boiler
The THISION L boiler consists of the
following main components:
1 Casing
2 Control panel
3 Flue gas connection (+ test point)
4 Air intake connection (+ test point)
5 Flow water connection
6 Return water connection
7 Gas connection
8 Syphon
9 Input for wiring
10 Connection for safety valve
11 Connection for fill/drain valve
12 Manometer
13 Fan
14 Gas valve
15 Ignition and ionisation electrodes
16 Heat exchanger
17 Inspection window
18 Ignition transformer
19 Electrical input connections
20 Controller
21 Condensate receptacle
Operating principle
The THISION L is a fully modulating
boiler. The control unit of the boiler
adapts the modulation ratio automati-
cally to the heat demand requested by
the system. This is done by controlling
the speed of the fan. As a result, the
Whirlwind mixing system will adapt the
gas ratio to the chosen fan speed, in
order to maintain the best possible
combustion figures and therewith the
best efficiency. The flue gases created
by the combustion are transported
downwards through the heat exchanger
The LMS14 control unit can control the
boiler operation based on:
Boiler control (stand alone operation);
weather compensated operation
(with optional outdoor sensor);
with 0-10V external influence
(temperature or capacity) from a buil-
ding management system.
and leave the boiler at the top into the
chimney connection.
The return water from the system en-
ters the boiler in the lower section,
where is the lowest flue gas tempera-
ture in the boiler. In this section con-
densation takes place. The water is
being transported upwards through the
heat exchanger, in order to leave the
boiler at the flow connection. The cross
flow working principle (water up, flue
gas down) ensures the most efficient
combustion results.
2
4
1
3
5 6
8 7
9
10 11
12
13
14
15
16
17
18
19
20
21
2

Technical data
5
THISION L
65
THISION L
85
THISION L
100
THISION L
120
THISION L
145
Nominal heat output at 80/60ºC max/min kW 60.8/10.1 81.1/13.4 92.9/15.6 111.6/18.7 132.2/23.3
Nominal heat output at 75/60ºC max/min kW 60.9/10.1 81.3/13.4 93.1/15.6 111.8/18.7 132.5/23.3
Nominal heat output at 40/30ºC max/min kW 63.9/11.1 85.3/14.8 100.0/17.2 120.0/20.6 142.3/25.6
Nominal heat input Hi max/min kW 62.4/10.4 83.3/13.8 95.2/16.0 114.3/19.2 135.5/23.9
Efficiency at 80/60ºC % 97.4 97.4 97.6 97.6 97.6
Efficiency at 40/30ºC % 102.4 102.4 105.0 105.0 105.0
Annual efficiency (NNG 75/60ºC) % 106.2 106.2 106.2 106.2 106.2
Annual efficiency (NNG 40/30ºC) % >110 >110 >110 >110 >110
Standstill losses (Twater = 70ºC) % 0.20 0.20 0.20 0.20 0.20
Max. condensate flow l/h 3.5 4.8 6.4 7.7 9.1
Gas consumption G20 max/min (10,9 kWh/m3) m3/h 5.7/1.0 7.6/1.3 8.7/1.5 10.5/1.8 12.4/2.2
Gas consumption G25 max/min (8,34 kWh/m3) m3/h 7.5/1.2 10.0/1.7 11.4/1.9 13.7/2.3 16.3/2.9
Gas consumption G31 max/min (12,8 kWh/kg) kg/h -/- -/- -/- -/- -/-
Gas pressure G20 mbar 20 20 20 20 20
Gas pressure G25 mbar 25 25 25 25 25
Gas pressure G31 mbar -/- -/- -/- -/- -/-
Maximum gas pressure mbar 50 50 50 50 50
Flue gas temperature at 80/60ºC max/min ºC 76/63 76/63 76/63 76/63 76/63
Flue gas temperature at 40/30ºC max/min ºC 55/39 55/39 55/39 55/39 55/39
Flue gas quantity max/min m3/h 119/19 159/25 178/29 213/35 253/44
CO2 level G20/G25 max/min % 8.5/8.5 8.5/8.5 8.7/8.5 8.7/8.5 8.7/8.5
CO2 level G31 max/min % -/- -/- -/- -/- -/-
NOx level mg/kWh 39 39 39 39 39
CO level max/min mg/kWh 98/7 98/7 98/7 98/7 98/7
Max. permissible flue resistance max/min Pa 150/15 150/15 150/15 200/15 200/15
Water volume l 4.0 4.7 6.5 8.0 9.4
Water pressure max/min bar 8/1.5 8/1.5 8/1.5 8/1.5 8/1.5
Max. water temperature (High limit thermostat) ºC 100 100 100 100 100
Maximum temperature setpoint ºC 90 90 90 90 90
Nominal water flow at dT=20K m3/h 2.6 3.4 4.0 4.8 5.6
Hydraulic resistance at nominal water flow kPa 16 29 15 22 34
Electrical connection V 230 230 230 230 230
Frequency Hz 50 50 50 50 50
Mains connection fuse A 10 10 10 10 10
IP class - IPX4D IPX4D IPX4D IPX4D IPX4D
Power consumption boiler max/min (excl. pump) W 98/26 167/38 195/30 228/36 248/44
Power consumption 3-step pump (optional) W 150 205 150 210 385
Power consumption speed controlled pump (opt) W 124 124 130 130 130
Weight (empty) kg 60 68 80 90 97
Noise level at 1 meter distance* dB(A) 56/50 56/50 56/50 56/50 56/50
Ionisation current minimum µA 3 3 3 3 3
PH value condensate - 3.2 3.2 3.2 3.2 3.2
CE certification code -
Water connections - R1.1/4" R1.1/4" R1.1/2" R1.1/2" R1.1/2"
Gas connection - R3/4" R3/4" R1" R1" R1"
Flue gas connection mm 100 100 100 100 130
Air intake connection (for room sealed use) mm 100 100 100 100 130
Condensate connection mm 22 22 22 22 22
CE-0063CM3576
THISION L
50
45.7/7.7
45.8/7.7
48.0/8.4
46.9/7.8
97.4
102.4
106.2
>110
0.20
2.6
4.3/0.7
5.6/0.9
-/-
20
25
-/-
50
76/63
55/39
89/14
8.5/8.5
-/-
39
98/7
150/15
4.0
8/1.5
100
90
1.9
9
230
50
10
IPX4D
98/26
150
124
60
56/50
3
3.2
R1.1/4"
R3/4"
100
100
22
* non room sealed / room sealed

Technical data
6
Dimensions TH-L 50
TH-L 65
TH-L 85 TH-L 100 TH-L 120 TH-L 145
B mm 490 490 590 590 590
B1 mm 140 140 140 140 190
B2 mm 245 245 295 295 295
D mm 500 500 600 600 600
H mm 810 810 950 950 950
W1 mm R 1 1/4" R 1 1/4" R 1 1/2" R 1 1/2" R 1 1/2"
W2 mm R 1 1/4" R 1 1/4" R 1 1/2" R 1 1/2" R 1 1/2"
G mm R 3/4" R 3/4" R 1" R 1" R 1"
F mm 100 100 100 100 130
A mm 100 100 100 100 130

Extent of delivery
Standard boiler
Accessories
7
Standard boiler
A boiler delivery package contains the
following components:
Extension module AGU2.550 for
heating zone control or external gas
valve and/or room fan control in com-
bination with an alarm signal.
For each boiler a maximum of 3
AGU2.550 modules (2x heating zone,
1x ext. gas valve / room fan in combi-
nation with alarm) can be integrated
in the boiler;
Additional RVS63 heating zone con-
troller, when controlling more than 2
zones (incl. wall hung box, all neces-
sary sensors and sockets and con-
nection material for bus communica-
tion).
The above accessories are specially
designed for the THISION L boiler and
therewith easy to install (plug and play).
By choosing a combination of the kits
mentioned above, you can create your
own complete system solution. Ask
your supplier for more detailed informa-
tion.
Component Pcs. Package
Boiler fully assembled and tested 1 Cardboard box on pallet
Mounting bracket incl. mounting material 1 Together with manuals, in folding box inside boiler
packaging
Syphon for condensate connection 1 Inside boiler packaging
Operation and Installation manual 1 Map packed in cardboard box in boiler packaging
Spare parts list 1 Map packed in cardboard box in boiler packaging
Wiring diagram 1 Map packed in cardboard box in boiler packaging
Accessories
Additional to the boiler, the following
accessories can be ordered:
Standard 3-step pump incl. connec-
tion kit;
Speed controlled pump incl. connec-
tion kit;
Safety valve, fill/drain valve and con-
nection for expansion tank;
Set with water (2x) and gas (1x)
cocks;
Gas filter incl. connection kit;
Min. gas pressure switch;
Plate heat exchanger (dT=10K/15K or
dT=20K) incl. connection kit;
Low velocity header, suitable for
dT=10K/15K and dT=20K incl. con-
nection kit;
Plug & play cascade kit (see cascade
manual for more details);
Extension module AGU2.551 for
0-10V control of a modulating pump
and/or boiler capacity feedback to a
building management system;
Electrical connection for external gas
valve and/or room fan.

Installation
Boiler transport
Removing the casing
8
Boiler transport
The THISION L boiler will be supplied
as a complete unit being fully assem-
bled and pre-tested. The packaging
dimension is 1050x572x575mm for
boiler types 50-85 and
1185x674x665mm for boiler types 100-
145, which makes it possible to trans-
port all models through a normal door
in one piece.
The THISION L can be transported with
a crane, but it has to be ensured that
the boiler is packed and fixed on a pal-
let. The straps must be connected to
the pallet.
Removing the casing
Remove the casing before installing the
boiler, in order to avoid damage to the
casing parts. Removing the casing is
done as shown on the pictures.
1
2
3
4

Installation
Boiler installation
Connecting the boiler
9
Boiler installation
The boiler should be positioned in a
frost-proof boiler room. If the boiler
room is on the roof, the boiler itself may
never be the highest point of the instal-
lation.
When positioning the boiler, please
note the recommended minimum clea-
rance in the picture. When the boiler is
positioned with less free space, mainte-
nance activities will be more difficult.
Connecting the boiler
This chapter will explain how to make
all connections to the boiler with regard
to:
Hydraulic connections
Condensate drain connection
Gas connection
Flue gas connection
Air intake connection
Electrical connection
The boiler should always be connected
in such a way, that the system applies
to all relevant standards and regulati-
ons (European, national and local). It’s
the responsibility of the installer to en-
sure that all standards and regulations
are respected.
Hydraulic connections (1,2,3,4)
The boiler should always be connected
in such a way, that water flow through
the boiler can be ensured at all times.
Connect the flow (1) and return (2) con-
nection of the system tension free to
the boiler connections.
The boiler contains a connection possi-
bility for an (optional) kit with safety
valve, fill/drain valve and an expansion
tank connection. The safety valve must
be connected to the flow connection (3)
of the boiler, the fill/drain valve and
expansion tank connection must be
connected to the return connection (4).
The (optional) pump kit should be
mounted directly to the return connecti-
on (2) of the boiler, before connecting
to the system.
Condensate connection (5)
After filling with water, the syphon
(included in delivery) should be in-
stalled to the connection (5) at the bot-
tom of the boiler. Connect the hose to
the draining system in the boiler room.
The connection to the draining system
should always be done with an open
connection, in order to avoid a flooding
of the boiler in case of a blocked drain.
Gas connection (6)
The gas connection must be made by
an authorized installer in accordance
with the applicable national and local
standards and regulations.
Connect the gas line from the system
tension free to the gas connection (6) of
the boiler. A gas cock should be moun-
ted directly behind the boiler.
A gas filter can be mounted directly on
the gas connection of the boiler.
1 2
5 6
3 4

11
Installation
Wiring diagram - Boiler
Optional
0-10V
Optional
Zone 1
Optional
Alarm
Optional
Zone 2
Optional
QAA75
Internal fuse LMS ist 2x T6.3A H 250V
Max. total current at 230VAC T25 is 5A
Flow sensor
Return sensor
Min. water
pressure switch
QX2 free programmable
230VAC +10% -15%
5mA… 1A, cosφ > 0.8
Alarm output
QX1
230VAC +10% -15%
5mA… 1A, cosφ > 0.8
AUX2
230VAC
5A
AUX1
230VAC
5A
QX3
230VAC +10% -15%
5mA… 1A, cosφ > 0.8
DHW pump
Power supply
230VAC +10% -15%
50HZ 10A
X18
230VAC
5mA… 1A, cosφ > 0.6
Lockout input
*1
Temp./capacity ext. input
0.15-10VDC
Outdoor sensor
DHW thermostat or
sensor *2
Flue gas sensor
Header sensor
Interlock input
Boiler enable
Low voltage contacts according to standards and directives for
SELV.
*1 When connecting, remove jumper or resistor
*2 Optional, see “Accessories”
*3 When connecting a thermostat, high quality contact
material is required!
(e.g. gold plated contacts)
Thermostat
Type 50 Type 65-145
Ø Lmax
0,25 mm2 20 m
0,5 mm2 40 m
1,0 mm2 80 m
1,5 mm2 120 m
Cable cross-sectional area for
external sensors, see table.

Installation
Wiring diagram - Accessories
12
Optional
Alarm
M-UX41 Speed controlled pump
0-10VDC Imax. 3mA SELV
M-UX42 Boiler output signal
0-10VDC Imax. 3mA SELV
Optional
Pump
3-speed
Optional
Zone 1
Optional
Zone 2
Optional
Pump
PWM
Optional
Pump
0-10V
Boiler types 50-85 Boiler types 100-145 *
* Option is also used for boiler output signal
for boiler types 50-85.
Imax. = 3mA
blue
brown
yellow-green
Jumper “mode UX42”; b
blue
brown
yellow-green
blue or
white brown
blue
brown
yellow-green
brown
white
Not used:
blue and black
Module 3
Alarm
230VAC
(max. 1A)
Module 2 Module 1
Pump Mixing
valve
Flow
sensor
Pump Mixing
valve
Flow
sensor

Commissioning
Water and hydraulic system
13
Water quality
The system should be filled with water
with a PH value between 8,0 and 9,5.
The chloride value of the water should
not exceed 50 mg/l. Entry of oxygene
by diffusion should be prevented at all
times. Damage to the heat exchanger
because of oxygene diffusion will not
be taken under warranty.
Water pressure
Open the valves to the system. Check
the water pressure in the system. If the
water pressure is too low (see table
below), increase the pressure up to at
least the minimum required water
pressure in the table.
Filling can eventually be done via the
(optional) fill and drain valve (2) on the
return connection (1) of the boiler.
Hydraulic system
Check if the boiler is hydraulically con-
nected to the system in such way, that
water flow can be secured at all times
during burner operation. The water flow
is supervised by ∆T-protection in the
boiler and a lack of flow will lead to a
direct burner stop and lockout of the
boiler.
Commissioning of the boiler should be
carried out by authorized personnel
only. Failure to respect this condition
makes the guarantee void. A protocol
of the commissioning should be filled
out (see end of this chapter for example
of commissioning protocol).
This chapter explains the commissio-
ning of the boiler with the standard boi-
ler controller. When an additional sys-
tem controller is installed, please refer
to its manual for commissioning the
controller.
In installations with higher water volu-
mes, it’s necessary to respect the maxi-
mum filling and additional volumes with
corresponding hardness values as sta-
ted in the german VDI2035 standard. In
the table you can find the nominal va-
lues for filling and additional water for
the THISION L according to the the
VDI2035.
The table at the left gives an indication
of the relation between the water quali-
ty and the maximum water filling volu-
me during the lifetime of the boiler.
Consult the original text of the VDI2035
for more detailed information.
1
2
Boiler output Max. sum of alkaline earths
[kW] [mol/m3] [ºdH] [ºf]
50 - 200 2.0 11.2 20
200 - 600 1.5 8.4 15
Max. total hardness
Concentrate
Ca(HCO3)2
Capacity of installation Q (kW)
150 200 250 300 400 500 600
mol/m3 ºf Maximum water (re)fill volume Vmax [m3]
≤0.5 ≤5 - - - - - - -
1.0 10 - - - - - - -
1.5 15 3 4 5 6 8 10 12
2.0 20 3 4 5 6 6.3 7.8 9.4
2.5 25 1.9 2.5 3.1 3.8 5.0 6.3 7.5
≥3.0 ≥30 1.6 2.1 2.6 3.1 4.2 5.2 6.3
ºdH
≤2.8
5.6
8.4
11.2
14.0
≥16.8
Minimum operating
pressure
[bar]
Flow tempe-
rature
[ºC]
> 1.5 90

Commissioning
Gas supply
Condensate connection
Flue and air intake connections
14
Gas supply
Check the gas supply connection to the
boiler for tightness. If any leakage is
found, reseal the leakage before star-
ting the boiler!
Remove any air between the gas valve
and the gas line. This can be done at
the test point (1) at the gas pressure
switch. Don’t forget to close the test
point afterwards!
Check the gas type and values with the
local gas company, in order to know for
which gas type the boiler should be
commissioned.
Condensate connection
Remove the syphon (2) from the con-
densate connection. Fill it with water
and place it back in the original positi-
on. Make sure the syphon is filled befo-
re starting the boiler, in
order to prevent flue gases discharging
through the condensate connection!
Flue and air intake connections
Check whether the flue and air intake
systems are made according to the
national and local regulations. Installati-
ons which don’t comply with the regula-
tions, are not allowed to be commissio-
ned.
Make sure that all connections are free.
The size of flue gas and air intake con-
nections may not be reduced.
1
2

Commissioning
Prepare boiler for first startup
15
Legend:
A On/off switch
B Return (ESC)
C Room temperature control
D Confirmation (OK)
E Manual mode
F Chimney sweeper mode
G Info mode
H Reset button
I Operation mode heating zone(s)
L Display
M Operation mode DHW
Preparation for first startup
Open the gas supply;
Enable the power supply to the boiler;
Switch on the boiler with the on/off
switch (A);
Make sure the boiler is in standby
mode (K);
Check the pump operation: make
sure the pump runs in the right
direction;
Release all air from the pump motor.
It‘s recommended to put the boiler on
50% load after the first startup, as this
is the best starting point to do a proper
combustion analysis. This can be done
with the following procedure:
Push button I >3 Sek, the boiler goes
into controller Stopp mode.
Push the Info button (G), the actual
boiler load (%) appears in the display;
Choose „set up“ (confirm with OK
button), now the boiler load can be
changed by rotating the wheel (C)
and confirming the 50% setting with
the OK button.
After checking the combustion values
(see next page), the controller Stopp
mode can be stopped by pushing the
control mode button (I) >3 Sek.
A
M
A
H
B C D E F
I
L
G

Commissioning
Combustion analysis
16
Combustion check at full load
Start the boiler in controller stop mode
and go to 50% load. Now the boiler
operates at 50% load. Allow the boiler
to stabilise the combustion for 3
minutes. Then increase the boiler load
step by step up to 100%. Check the
gas pressure on the inlet of the gas
valve while increa-sing the boiler load:
the gas pressure should never go
below the minimum required value
see technical data. When an (optional)
minimum gas pressure switch is con-
nected, this must be set to 75% of the
required gas pressure.
Check the combustion settings via the
test point in the chimney connection
(1). If necessary, correct the settings
with the small adjustment screw at the
top of the gas valve (2).
Combustion check at minimum load
Switch the boiler to minimum load (0%).
Check the combustion settings the
same way as described for full load. If
necessary, correct the settings with the
large adjustment screw at the top of the
gas valve (3).
Combustion check at 50% load
An additional reference check of com-
bustion values at 50% load is recom-
mended in order to check if the gas
valve is set in such way, that the modu-
lating behaviour is normal. The CO2
value should be in between the settings
of full load and minumum load. CO
value should be equal to full load and
minimum load values.
Make sure that the boiler is set to auto-
matic operation and controller stop mo-
de is disabled after the combustion test
is finished.
1
2
3
Combustion settings max. load
for natural gas G20 / G25
TH-L 50-145
CO2, max % 8.5 ± 0.2
Combustion settings min. load
for natural gas G20 / G25
TH-L 50-145
CO2, min % 8.5 ± 0.2

Commissioning
Check water flow
17
qactual = (∆Tnominal / ∆Tmeasured) * qnominal [m3/h]
Check water flow
The water flow through the boiler can
be checked with two different methods
shown below.
∆T measurement
Check the temperature difference over
the boiler (∆T flow-return) when the
boiler is running on 100% load. The
nominal ∆T is 20K and must be at least
between 10K and 20K for secure boiler
operation. An indication of the actual
flow rate can be found with the follo-
wing calculation (see table below for
nominal data):
qactual = √(∆pmeasured / ∆pnominal) * qnominal [m3/h]
∆p measurement
Check the pressure difference over the
boiler (∆p flow-return) when the boiler
pump is running (burner on is not requi-
red). The nominal ∆p for each boiler
type can be found in the table below,
actual ∆p must be within:
1.0*Δpnenn ≤ ∆P ≤ 4.0*∆pnenn. An indi-
cation of the actual flow rate can be
found with the following calculation (see
table below for nominal data):
Water flow data
TH-L 50 TH-L 85 TH-L 100 TH-L 120 TH-L 145
Nominal flow rate m3/h 1.9 3.4 4.0 4.8 5.6
∆T at nominal flow rate K 20
∆p at nominal flow rate kPa 9 29 15 22 34
TH-L 65
2.6
16

Commissioning
Check functionality of safety devices
Gas tightness check
Boiler shut down
18
Flow temperature sensor (1)
Disconnect the plug from the sensor
while the boiler is switched on. This
should result in a lockout no. 20.
The lockout should disappear as soon
as the plug is placed back in position,
the boiler will restart.
Return temperature sensor (2)
Disconnect the plug from the sensor
while the boiler is switched on. This
should result in a lockout no. 40.
The lockout should disappear as soon
as the plug is placed back in position,
the boiler will restart.
Flue gas temperature sensor (3)
Disconnect the plug from the sensor
while the boiler is switched on. This
should result in a lockout no. 28.
The lockout should disappear as soon
as the plug is placed back in position,
the boiler will restart.
Ionisation electrode (4)
Remove electrical connection from the
ionisation electrode while the boiler is
running, the boiler will go in lockout no.
128. The boiler will try to restart. With
the electrical connection removed, the
restart will result in lockout no. 133.
When the connection is already
mounted, the restart will be successful.
Measuring the ionisation current can
be done by mounting a multi-meter (set
to µA) in between the ionisation elec-
trode and its electrical connection. The
ionisation current should always be
above 1.2 µA, in normal conditions it
will be 6 µA and above.
Check functionality of safety devices
All safety devices have to be checked
on good functioning. Safety devices on
a standard boiler are a water flow tem-
perature sensor, water return tempera-
ture sensor, fluegas temperature sen-
sor and ionisation electrode. These
devices can be checked as described
below.
Gas tightness check
Check the gas tightness of all sealed
connections with an approved soap or
electronic gas analyzer, for example:
Test points;
Bolt connections;
Gaskets of mixing system, etc.
Boiler shut down
When the boiler will not be used for
longer periods, shut down the boiler by
following procedure:
Switch the boiler in standby operation
(K);
Switch off the boiler with the on/off
switch (5);
Disable power supply to the boiler by
deactivating the mains isolator switch
in the boiler room;
Close the gas supply to the boiler.
1
2
3
4
5

Commissioning
Commissioning protocol
19
Commissioning Protocol THISION L
Project
Boiler type Project
Serial number Address
Year City
Nominal load (Hi) [kW] Date
Nominal output (Hi) [kW] Engineer
System
Water pressure [bar] Installati-
on:
Roof top
Water pH [-] Ground floor
Water hardness [ºdH] Basement
Water chloride [mg/l] Other: .........................
Water ∆T full load [ºC] Hydrau-
lics:
Low velocity header
Water ∆pboiler [kPa] Plated heat exchanger
Water flow [m3/h] Bypass boiler
Pump setting [-] Other: .........................
Safety devices
High limit setting [ºC] Water flow sensor checked
Temp. limiter setting [ºC] Fluegas sensor checked
Min. gas pressure switch setting [mbar] Water flow switch checked
Ignition time burner [sec]
Combustion analysis
100% load 50% load Min. load
Gas consumption [m3/h] [m3/h] [m3/h]
Gas pressure [mbar] [mbar] [mbar]
CO2 [%] [%] [%]
O2 [%] [%] [%]
CO [ppm] [ppm] [ppm]
NOx [ppm] [ppm] [ppm]
Tatmospheric [ºC] [ºC] [ºC]
Tfluegas [ºC] [ºC] [ºC]
Twater, flow [ºC] [ºC] [ºC]
Twater, return [ºC] [ºC] [ºC]
Ionisation current [µA] [µA] [µA]
pfan [mbar] [mbar] [mbar]
ptop panel [mbar] [mbar] [mbar]
pcombustion chamber [mbar] [mbar] [mbar]
Remarks

Operating instructions
Controls
20
Confirmation (OK) (D)
Return (ESC) (B)
These buttons are used for program-
ming in combination with the wheel.
By pressing the ESC button it‘s possible
to go back one level, changed values
are not taken over by the controller.
By pressing the OK button it‘s possible
to arrive in the next level or confirm
changed values.
Manual mode (E)
This button is used for switching the
boiler into manual mode. In manual
mode all pumps will run and the mixing
valves are no longer controlled, the bur-
ner setpoint is 60°C (indicated by span-
ner symbol).
On/off switch (A)
Position 0:
Boiler and connected electrical compo-
nents are no powered. Frost protection
is not secured.
Position I
The boiler and connected electrical
components are powered and standby
for operation.
Operation mode DHW (M)
For switching on the DHW operation
(indication in display below DHW sym-
bol)
Operation mode heating zone(s) (I)
For setting 4 different heating modes:
Auto (clock): Automatic operation by
time programm
Comfort (sun): 24/7 heating in comfort
mode
Reduction (moon): 24/7 heating in re-
duced mode
Standby: heating off, frost protection
activated.
Display (L)
Info mode (G)
Display possibility of following info
without influence on boiler control:
temperatures, operation mode
Heating / DHW, error code.
Room temperature control (C)
for changing room comfort tempe-
rature
for changing settings when pro-
gramming.
Deaeration mode (E)
By pressing the manual mode button
longer than 3 seconds, the automatic
hydraulic deaeration is activated. During
deaeration the system is put in standby
mode
The pumps are switched on and off for
several times.
After deaeration, the boiler automatically
returns to normal operation.
Chimney sweeper mode (F)
Used for combustion analysis. By pres-
sing the button once again, or automati-
cally after 15 minutes, the chimney swee-
per mode will be deactivated (indicated
by spanner symbol).
Reset button (H)
By shortly pressing the reset button a
burner lockout can be cancelled.
Legend:
A On/off switch
B Return (ESC)
C Room temperature control
D Confirmation (OK)
E Manual mode
F Chimney sweeper mode
G Info mode
H Reset button
I Operation mode heating zone(s)
L Display
M Operation mode DHW
M
A
H
B C D E F
I
L
G

21
Operating instructions
Display / Programming
- gewünschtes Menü
auswählen
- mit Taste OK bestätigen
- mit Taste ESC zurück
zur Grundanzeige
- gewünschte Benutzer-Ebene auswählen
- mit Taste OK bestätigen
- gewünschtes Menü auswählen
- mit Taste OK bestätigen
- mit Taste ESC zurück zur Grundanzeige
DHW mode selection
Heating operation mode selection
(Controller Stopp mode when
pressing > 3 sec.)
Display
Info button
Confirm
Manual mode
(Deaeration mode when pressing
> 3 sec.)
Chimney sweeper mode
Enduser
- choose menu
- confirm with OK button
- choose parameter
- confirm with OK button
- change value + - with wheel
- confirm with OK button
- return to main menu with ESC button
Commissioning Expert
- choose user level
- confirm with OK button
- choose menu
- confirm with OK button
- choose parameter
- confirm with OK button
- change value + - with wheel
- confirm with OK button
- return to main menu with ESC button
Programming
Select
(turn left/right)
Quit menu
Reset
Press OK (1x)
Press OK (1x)
Press INFO (4 sec.)
Default mode
(buttons)
Heating to comfort setpoint Info level activated
Heating to reduced setpoint Programming
activated
Heating for frost protection setpoint Heating
temporarily switched off
Process running – please weit ECO function
active
Burner operating (only oil / gas boiler)
Error messages
Info level activated
Programming activated
Heating temporarily switched off
ECO function active
Holiday function active
Reference to heating circuit
Maintenance / special operation
Parameter number

22
Operating instructions
Overview of main functions
Button Action Procedure Display / Function
Set room temperature
Zone 1 and zone 2
Actuate wheel left/right
Turn wheel
Confirm with OK button
or wait 5 sec.
or press
Comfort setpoint with blinking temperature
Blinking temperature in 0,5 °C steps from 10 to 30 °C
Comfort setpoint saved
Comfort setpoint cancelled
- after 3 sec. Main menu appears
Set room temperature for
zone 1 or zone 2
Zone 2 independent from zone 1
Actuate wheel left/right
Confirm with OK button
Actuate wheel left/right
Confirm with OK button
or wait 5 sec.
or press
Choose heating zone
Heating zone is chosen
Blinking temperature in 0,5 °C steps from 10 to 30 °C
Comfort setpoint saved
Comfort setpoint cancelled
- after 3 sec. Main menu appears
Switch on /off DHW ope-
ration
Press button DHW mode on / off
(see indication below DHW symbol)
- On: DHW mode by time programm
- Off: no DHW operation
- Safety functions activated
Change heating operation
mode
Factory setting
Press button 1x
Press button 1x again
Press button 1x again
Automatic mode on, with:
- Heating by time programm
- Temperature setpoint by heating programm
- Safety functions activated
- Summer/Winter automatic switching activated
- ECO-functions activated
(see indication below operation symbol)
Continuous COMFORT heating on, with:
- Heating without time programm by comfort setpoint
- Safety functions activated
Continuous REDUCED heating on, with:
- Heating without time programm by reduced setpoint
- Safety functions activated
- Summer/Winter automatic switching activated
- ECO-functions activated
Safety mode on, with:
- Heating off
- Temperature by frost protection
- Safety functions activated
Controller Stop mode Press button > 3 sec.
Press button > 3 sec. again 304: Controller Stopp mode insert setpoint
after 3 sec. Main menu appears
Info display
Press button 1x
Press button 1x again
Press button 1x again
…..
Press button 1x
INFO Segment displayed
- Status Boiler - room temperature
- room temperature minimum
- Status DHW - room temperature maximum
- Status zone 1 - outside temperature
- Status zone 2 - outside temperature minimum
- outside temperature maximum
- Time / Date - DHW temperature 1
- Error indication - Boiler temperature
- Maintenance indication - Flow temperature
(Info display depends on configuration)
Back to main menu; INFO Segment disappears
Operation by manual
setpoint
Change factory setting
boiler temperature
Press button 1x
Press button
Press button
Turn wheel -/+
Press button
Press button
Press button
Manual mode on (spanner symbol appears)
- Haeting by fixed setpoint
(factory setting = 60 °C)
301: Manual mode insert setpoint?
blinking temperature
set value
Status boiler
Manual mode off (spanner symbol disappears)
Deaeration Press button > 3 sec.
Press button > 3 sec. again 312: Deaeration on
Deaeration off
Activate chimney sweeper
mode Press button (< 3 sec.)
Press button again (< 3 sec.) Chimney sweeper mode on
Chimney sweeper mode off
Temporary reduction of
reduced temperature on
QAA75
Press button
Press button again Heating by reduced setpoint
Heating by comfort setpoint
RESET Reset button Press button (< 3 sec.)
Press button again > 3 sec. Boiler manually blocked, no release
Boiler released, Alarm symbol disappears
= confirmation
= cancel, return to main
menu

Maintenance
Cleaning the condensate receptacle
Cleaning and refilling the syphon
Inspection of combustion chamber
24
Cleaning the condensate receptacle
Disconnect the plug of the fluegas
temperature sensor (1);
Remove the condensate receptacle
(2);
Clean the receptacle;
Mount the condensate receptacle;
Connect the plug of the fluegas tem-
perature sensor.
Cleaning and refilling the syphon
Remove the syphon (3) from the con-
densate connection;
Clean and fill it with fresh water;
Mount the syphon back in the original
position.
Inspection of combustion chamber
For inspection of the combustion cham-
ber the mixing system and burner must
be disassembled.
Switch off the boiler and close the gas
supply;
Remove the electrical connection
from the fan and gas valve (4);
Remove the electrical connection
from the electrodes (5);
Undo the gas connection at the inlet
of the gas valve (6);
Disassemble the top plate incl. mixing
system (7);
Remove the burner from the
combustion chamber (8);
Inspect the combustion chamber and
clean it with a vacuumcleaner if
necessary;
Assemble all components in opposite
order;
Open the gas supply and check all
connections for gas leakage;
Switch on the boiler.
1
2
5
4
6
7
8
3

Maintenance
25
Water pressure and quality
Check if the water pressure and quality
meet the requirements. Consult the
chapter “commissioning: water and
hydraulic system” for more detailed
information.
Water flow rate
Check if the water flow rate through the
boiler is within the limits. Consult the
chapter “commissioning: check water
flow” for more detailed information.
Combustion analysis
Check the combustion at full load and
minumum load, correct the settings if
necessary. An additional reference
check at 50% load is recommended.
Consult the chapter “commissioning:
combustion analysis” for more detailed
information.
Gas pressure
Check the dynamic pressure of the gas
supply to the boiler, when the boiler is
running at full load. In case of a boiler
cascade, all boilers should be running
at full load. See technical data for re-
quired values.
Gas tightness check
Check the tightness of all sealed con-
nections with an approved soap or
electronic analyzer, for example:
Test points;
Bolt connections;
Gaskets of mixing system, etc.
Safety devices
Check the functionality and the settings
of all safety devices connected. Consult
the chapter “commissioning: Check
functionality of safety devices” for more
detailed information.

Maintenance
Maintenance Protocol
26
Maintenance Protocol THISION L
Project
Boiler type Project
Serial number Address
Year City
Nominal load (Hi) [kW] Date
Nominal output (Hi) [kW] Engineer
System
Water pressure [bar]
Water pH [-]
Water hardness [ºdH]
Water chloride [mg/l]
Water ∆T full load [ºC]
Water ∆pboiler [kPa]
Water flow [m3/h]
Pump setting [-]
Safety devices
High limit setting [ºC] Water flow sensor checked
Temp. limiter setting [ºC] Fluegas sensor checked
Min. gas pressure switch setting [mbar] Water flow switch checked
Ignition time burner [sec]
Combustion analysis
100% load 50% load Min. load
Gas consumption [m3/h] [m3/h] [m3/h]
Gas pressure [mbar] [mbar] [mbar]
CO2 [%] [%] [%]
O2 [%] [%] [%]
CO [ppm] [ppm] [ppm]
NOx [ppm] [ppm] [ppm]
Tatmospheric [ºC] [ºC] [ºC]
Tfluegas [ºC] [ºC] [ºC]
Twater, flow [ºC] [ºC] [ºC]
Twater, return [ºC] [ºC] [ºC]
Ionisation current [µA] [µA] [µA]
pfan [mbar] [mbar] [mbar]
ptop panel [mbar] [mbar] [mbar]
pcombustion chamber [mbar] [mbar] [mbar]
Remarks

27
In case of a lockout, a warning symbol ( ) and a flashing error code appears on the display. The cause of a fault should first
be determined and eliminated before the boiler is being reset. The table below shows all possible lockouts with indication of
possible cause.
Lockouts
Error
code
Description of error
0 No error
10 Outside temperature sensor error
20 Boiler temperature 1 sensor error
26 Common flow temperature sensor error
28 Flue gas temperature sensor error
30 Flow temperature 1 sensor error
32 Flow temperature 2 sensor error
38 Flow temperature primary controller sensor error
40 Return temperature 1 sensor error
46 Return temperature cascade sensor error
47 Common return temperature sensor error
50 DHW temperature 1 sensor error
52 DHW temperature 2 sensor error
54 DHW primary controller sensor error
57 DHW circulation temperature sensor error
60 Room temperature 1 sensor error
65 Room temperature 2 sensor error
70 Buffer storage tank temperature 1 sensor error
71 Buffer storage tank temperature 2 sensor error
72 Buffer storage tank temperature 3 sensor error
73 Collector temperature 1 sensor error
74 Collector temperature 2 sensor error
82 LPB address collision
83 BSB wire short-circuit
84 BSB address collision
85 BSB RF communication error
91 EEPROM error lockout information
98 Extension module 1 error (collective error)
99 Extension module 2 error (collective error)
100 2 clocktime masters (LPB)
102 Clocktime master without reserve (LPB)
103 Communication error
105 Maintenance message
109 Boiler temperature supervision
110 STB lockout
111 TW cutout
119 Safety thermostat on burner door interrupted
121 Flow temperature 1 (HC1) supervision
122 Flow temperature 2 (HC2) supervision
125 Pump supervision error
126 DHW charging supervision
127 Legionella temperature not reached
128 Loss of flame during operation
129 Fan error or LP error
130 Flue gas temperature limit exceeded
131 Burner fault
132 GP or LP error
133 No flame during safety time

Lockouts
28
Error
code
Description of error
146 Configuration error collective message
151 Internal error
152 Parameterization error
153 Unit manually locked
160 Fan error
162 LP error, does not close
164 Error heating circuit flow switch
166 LP error, does not open
171 Alarm contact H1 or H4 active
172 Alarm contact H2 (EM1, EM2 or EM3) or H5 active
173 Alarm contact H6 active
174 Alarm contact H3 or H7 active
178 Limit thermostat heating circuit 1
179 Limit thermostat heating circuit 2
183 Unit in parameterization mode
193 Pump supervision error after flame on
216 Fault boiler
217 Fault sensor
241 Flow sensor solar sensor error
242 Return sensor solar sensor error
243 Swimming pool temperature sensor error
270 Limit function
317 Mains frequency outside permissible range
320 DHW charging temperature sensor error
322 Water pressure too high
323 Water pressure too low
324 BX same sensors
325 BX / extension module same sensors
326 BX / mixing group same sensors
327 Extension module same function
328 Mixing group same finction
329 Extension module / mixing group same function
330 Sensor BX1 no function
331 Sensor BX2 no function
332 Sensor BX3 no function
333 Sensor BX4 no function
334 Sensor BX5 no function
335 Sensor BX21 no function (EM1, EM2 or EM3)
336 Sensor BX22 no function (EM1, EM2 or EM3)
337 Sensor BX1 no function
338 Sensor BX12 no function
339 Collector pump Q5 not available
340 Collector pump Q16 not available
341 Solar Collector sensor B6 not available
342 DHW sensor B31 not available
343 Solar integration not available
344 Solar controlling element buffer K8 not available
345 Solar controlling element swimming pool K18 not available

29
Lockouts
Error
code
Description of error
346 Solid fuel boiler pump Q10 not available
347 Solid fuel boiler comparison sensor not available
348 Solid fuel boiler address error
349 Buffer return valve Y15 not available
350 Puffer address sensor
351 Primary controller / system pump address error
352 Pressureless header address error
353 Common flow sensor B10 not available
371 Flow temperature 3 (heating circuit 3) supervision
372 Limit thermostat heating circuit 3
373 Extension module 3 error (collective error)
349 Buffer return valve Y15 not available
350 Puffer address sensor
351 Primary controller / system pump address error
352 Pressureless header address error
372 Limit thermostat heating circuit 3
373 Extension module 3 error (collective error)
386 Fan speed has lost valid range
388 DHW error no function
426 Feedback flue gas damper
427 Configuration flue gas damper
431 Sensor primary heat exchanger
432 Functional earth not connected
353 Common flow sensor B10 not available
371 Flow temperature 3 (heating circuit 3) supervision
433 Temperature primary heat exchanger to high

Betriebsanleitung
für die autorisierte Fachkraft
THISION L
08/2012 DOC3078 / 12103187

Inhalt
2
Inhalt .................................................................. 2
Sicherheitsbestimmungen Allgemeine Bestimmungen ...................... 3
Verwendungszweck ................................. 3
Normen und Vorschriften .......................... 3
Konstruktion Produktbeschreibung ................................ 4
Funktionsbeschreibung ............................. 4
Technische Daten .................................................................. 5
Lieferumfang Standard Ausführung ............................... 7
Zubehör .................................................... 7
Installation Transport ................................................... 8
Demontage Verkleidung ............................ 8
Installation ................................................. 9
Anschlüsse ................................................ 9
Schaltplan - Kessel .................................... 11
Schaltplan - Zubehör ................................. 12
Inbetriebnahme Wasser- und Hydrauliksystem .................. 13
Gasversorgung ........................................ 14
Kondensatanschluss ................................ 14
Abgas- und Zuluftanschlüsse ................... 14
Vorbereitung für 1. Inbetriebnahme ......... 15
Verbrennungswerte .................................. 16
Wasserdurchsatz prüfen .......................... 17
Sicherheitseinrichtungen prüfen ............... 18
Gasdichtheitsprüfung ............................... 18
Kessel außer Betrieb setzen .................... 18
Inbetriebnahme Protokoll ......................... 19
Bedienung Bedienelemente ....................................... 20
Beschreibung Display / Programmierung . 21
Kurzübersicht über die Hauptfunktionen ... 22
Wartung Checkliste ................................................ 23
Ersetzen der Elektroden .......................... 23
Reinigung der Kondensatwanne .............. 24
Reinigen und Auffüllen des Siphons ........ 24
Inspektion der Verbrennungskammer ...... 24
Wasserdruck und -qualität ....................... 25
Wasserdurchsatz ..................................... 25
Verbrennungswerte .................................. 25
Gasdruck .................................................. 25
Gasdichtheitsprüfung ............................... 25
Sicherheitseinrichtungen .......................... 25
Wartungsprotokoll .................................... 26
Störungen .................................................................. 27
Fühlerkennwerte .................................................................. 30
Konformitätserklärung .................................................................. 31

Sicherheitsbestimmungen
Allgemeine Bestimmungen
Verwendungszweck
Normen und Vorschriften
3
Allgemeine Bestimmungen
Diese Dokumentation enthält wichtige
Hinweise bezüglich Sicherheit und Zu-
verlässigkeit von Installation, Inbetrieb-
nahme und Betreibung des THISION L
Kessels. Alle beschriebenen Tätigkei-
ten sind ausschließlich durch die autori-
sierte Fachkraft auszuführen.
Es dürfen nur Original Bauteile des
Kesselherstellers verwendet werden,
ansonsten schließen wir unsere Ge-
währ- und Garantieleistungsbedingun-
gen aus.
Verwendungszweck
Der THISION L Heizkessel ist aus-
schliesslich für geschlossene Warm-
wasserheizungsanlagen zu verwenden.
Die maximale Temperatur des Kessel-
sollwerts beträgt 90ºC, sowie 100ºC
des Systems (Sicherheitstemperatur
Limit).
Normen und Vorschriften
Bei Installation und Betreibung des
THISION L Kessels müssen alle maß-
gebenden Normen (europäische und
nationale) eingehalten werden:
Lokale Gebäudevorschriften über die
Installation von Heizungsanlagen und
Abgassysteme
Vorschriften über den Anschluss an
das elektrische Versorgungsnetz
Vorschriften der lokalen Gasversor-
gungsunternehmen
Normen und Vorschriften betreffend
Sicherheitseinrichtungen für Hei-
zungsanlagen
Zusätzliche lokale Gesetze/Vorschrif-
ten bezüglich Installationen und
Betreibung von Heizungsanlagen.
Der THISION L Kessel ist CE geprüft
und beinhaltet die folgenden europä-
ischen Normen:
92 / 42 / EEC (Wirkungsgrade von
Warmwasserheizungsanlagen)
2009 / 142 / EEC
(Gasverbrauchseinrichtungen)
2006 / 95 / EEC (Sicherheit von elekt-
rischen Betriebsmitteln)
2004 / 108 / EEC (EMV Verträglich-
keit)
EN 483 (Anforderungen an Gasfeue-
rungsanlagen bis 70 kW)
EN 15420 (Anforderungen an Gas-
feuerungsanlagen – Type C Kessel
70 kW – 1000 kW)
EN 15417 (Spezielle Anforderungen
für kondensierende Gasheizkessel 70
kW – 1000 kW)
EN 50165
Elektrische Ausrüstung von nicht-
elektrischen Geräten für den Hausge-
brauch und ähnliche Zwecke -
Sicherheitsanforderungen
EN 15502-1 (Anforderungen an Gas-
feuerungsanlagen – Part 1: allgemei-
ne Anforderungen und Tests)
EN 55014-1 (2000) EMV – Anforde-
rungen an Haushaltgeräte, elektri-
sche Werkzeuge und ähnliche Appa-
rate – Teil 1: Emissionen
EN 55014-2 (1997) EMV – Anforde-
rungen an Haushaltgeräte, elektri-
sche Werkzeuge und ähnliche Appa-
rate – Teil 2: Sicherheit - Produktefa-
milienstandard
EN 61000-3-2 (2000) Elektromagneti-
sche Kompatibilität (EMC) - Teil 3-2:
Rahmenbedingungen - Rahmenbe-
dingungen für Stromschwankungen
(Stromaufnahme 16 A pro Phase)
EN 61000-3-3 (2001) Elektromagneti-
sche Kompatibilität (EMC) - Part 3-3:
Rahmenbedingungen für Spannungs-
schwankungen, Spannungsverluste
und –Flicker in öffentlichen Nieder-
spannungsnetzen, für Equipment mit
Nennstrom 16 A pro Phase, die kei-
ner Sonderanschlussbedingung un-
terliegen.
EN 60335-1 (2002) Haushalt und
ähnliche elektrische Geräte - Sicher-
heit-Teil 1: Allgemeine Anforderungen
EN 60335-2-102 (2006) Haushalt und
ähnliche elektrische Geräte - Sicher-
heit: Besondere Anforderungen für
Gas, Öl und Festbrennstoff gefeuerte
Geräte mit elektrischen Anschlüssen
Darüber hinaus sind die nationalen
Normen zu beachten:
Deutschland:
RAL - UZ 61 / DIN 4702-8
Schweiz:
SVGW
Vorschriften der kantonalen Instanzen
(z.B. Feuerpoilizeivorschriften)
Holland:
GASKEUR BASIS
GASKEUR SV
GASKEUR HR107
Belgien:
HR TOP

Installation
Kesseltransport
Demontage Verkleidung
8
Kesseltransport
Der THISION L ist ein vollausgerüste-
tes Kompaktheizgerät, welches vorein-
gestellt und geprüft ist.
Die Abmessungen der Verpackung ist
1050x572x575mm fur die Typen 50-85
und 1185x674x665mm für die Typen
100-145. Somit ist es möglich alle Mo-
delle durch eine normale Tür in einem
Stück zu transportieren. Der Heizkessel
kann seitwärts oder frontwärts mit ei-
nem Hubstapler aufgeladen und trans-
portiert werden.
Der THISION L kann mit einem Kran
transportiert wird, es muss aber sicher-
gestellt werden dass der Kessel in der
Verpackung auf eine Palette befestigt
ist. Die Lastgurte sollen an der Palette
angebracht werden.
Demontage Verkleidung
Vor Montage soll die Verkleidung des
Kessels demontiert werden um Be-
schädigungen zu vermeiden.
Die Demontage der Abdeckungen er-
folgt wie auf den Bildern dargestellt.
1
2
3
4

Installation
Schaltplan - Zubehör
12
Option
Alarm
M-UX41 Drehzahlgeregelte Pumpe
0-10VDC Imax. 3mA SELV
M-UX42 Leistungsrückmeldung
0-10VDC Imax. 3mA SELV
Option
Pumpe
3-stufig
Option
HK1
Option
HK2
Option
Pumpe
PWM
Option
Pumpe
0-10V
Kesseltypen 50-85 Kesseltypen 100-145 *
* Option wird auch verwendet für Leistungs-
rückmeldung bei Kesseltypen 50-85.
Imax. = 3mA
blau
braun
gelb-grün
Jumper “mode UX42”; b
blau
braun
gelb-grün
blau oder
weiss braun
blau
braun
gelb-grün
braun
weiss
Nicht verwendet:
blau und schwarz
Modul 3
Alarm
230VAC
(max. 1A)
Modul 2 Modul 1
Heizkreis-
pumpe
Mischer-
antrieb
Vorlauf-
fühler
Heizkreis-
pumpe
Mischer-
antrieb
Vorlauf-
fühler

Inbetriebnahme
Wasser– und Hydrauliksystem
13
Mindestbetriebs-
druck
[bar]
Vorlauf-
temperatur
[ºC]
> 1.5 90
Wasserqualität
Das System ist mit Wasser mit einem
pH-Wert zwischen 8,0 und 9,5 zu befül-
len. Der Chloridwert des Wassers darf
50 mg/l nicht überschreiten. Der Eintritt
von Sauerstoff durch Diffusion muss in
jedem Fall vermieden werden. Schäden
am Wärmetauscher durch eindringen-
den Sauerstoff fallen nicht unter die
Garantie.
Bei Systemen mit größeren Wasser-
mengen ist es notwendig, den Höchst-
füllstand und die zusätzlichen Mengen
mit entsprechender Härte gemäß der
deutschen Norm VDI2035 zu beachten.
In nebenstehender Tabelle sind die
Nennwerte für die Befüllung und zu-
sätzliches Wasser für den THISION L
gemäß der VDI2035 angegeben.
In der nebenstehender Tabelle sind
Angaben zum Verhältnis zwischen der
Wasserqualität und dem Höchstfüll-
stand für Wasser während der Stand-
zeit des Kessels enthalten. Bitte schla-
gen Sie im Originaltext der VDI2035 für
genauere Informationen nach.
Wasserdruck
Öffnen Sie die Ventile zum System.
Prüfen Sie den Wasserdruck im Sys-
tem. Wenn der Wasserdruck zu niedrig
ist (siehe unten stehende Tabelle), er-
höhen Sie den Druck mindestens auf
den Mindestwasserdruck laut Tabelle.
Die Befüllung kann eventuell erfolgen
über das (optionale) Füll- und Ablass-
ventil (2) am Rücklaufanschluss (1) des
Kessels.
Hydrauliksystem
Prüfen Sie, ob der Kessel hydraulisch
so an das System angeschlossen ist,
dass der Wasserdurchsatz jederzeit bei
Brennerbetrieb gesichert ist. Der Was-
serdurchsatz wird über eine ∆T-
Überwachung im Kessel überwacht.
Ein zu niedriger Durchsatz führt dazu,
dass der Brenner sofort stoppt und der
Kessel abschaltet.
Der Kessel wird ausschließlich von
befugtem Personal in Betrieb genom-
men. Die Garantie erlischt bei Nichtein-
haltung dieser Bedingung. Zur Inbe-
triebnahme ist ein Protokoll auszufül-
len.
In diesem Kapitel wird die Inbetriebnah-
me des Kessels mit einer Standardkes-
selsteuerung beschrieben. Sollte eine
zweite Systemsteuerung installiert sein,
beachten Sie bitte das entsprechende
Handbuch zur Inbetriebnahme des
Kessels.
1
2
Kesselleistung Max. Summe Erdalkali
[kW] [mol/m3] [ºdH] [ºf]
50 - 200 2.0 11.2 20
200 - 600 1.5 8.4 15
Max. Härte gesamt
Konzentrat
Ca(HCO3)2
Kapazität der Anlage Q (kW)
150 200 250 300 400 500 600
mol/m3 ºf Max. (Nach-) Füllmenge Wasser Vmax [m3]
≤0.5 ≤5 - - - - - - -
1.0 10 - - - - - - -
1.5 15 3 4 5 6 8 10 12
2.0 20 3 4 5 6 6.3 7.8 9.4
2.5 25 1.9 2.5 3.1 3.8 5.0 6.3 7.5
≥3.0 ≥30 1.6 2.1 2.6 3.1 4.2 5.2 6.3
ºdH
≤2.8
5.6
8.4
11.2
14.0
≥16.8

Inbetriebnahme
Vorbereitung für 1. Inbetriebnahme
15
Vorbereitung für 1. Inbetriebnahme
Öffnen Sie den Gasanschluss;
Betätigen Sie den Netztrennschalter,
um den Kessel mit Strom zu versor-
gen;
Schalten Sie den Kessel mit dem Ein-
/Ausschalter (A) ein;
Stellen Sie sicher, dass der Kessel im
Standby-Betrieb (K) bleibt;
Prüfen Sie die Pumpenfunktion: Stel-
len Sie sicher, dass die Drehrichtung
korrekt ist;
Lassen Sie alle Luft aus der Pumpe
ab, indem Sie die Verschlusskappe
am Pumpenmotorgehäuse entfernen.
Es wird empfohlen, den Kessel nach
der 1. Inbetriebnahme unter einer Aus-
lastung von 50 % zu betreiben, da die
Verbrennungsanalyse so am einfachs-
ten initiiert werden kann. Dies kann wie
folgt sichergestellt werden:
Betätigen Sie Taste I >3 Sek, hiermit
wird den Kessel auf Reglerstoppfunk-
tion geschaltet;
Betätigen Sie die Info-Taste (G), die
aktuelle Kesselleistung (%) erscheint;
Über „einstellen“ (bestätigen mit OK-
Taste) kann jetzt die Kesselleistung
verstellt werden, drehen Sie hierzu
den Drehschalter (C) und bestätigen
Sie den Wert 50% mit der OK-Taste.
Wenn die einstellungen der Inbetrieb-
nahme (siehe nächste Seite) beendet
sind, kann die Reglerstoppfunktion be-
endet werden durch Betätigung der
Betriebsartenschalter (I) >3 Sek.
M
A
H
B C D E F
I
L
G
Legende:
A Ein/Aus Schalter
B Rücksprungtaste (ESC)
C Raumtemperatur- Regulierknopf
D Bestätigungstaste (OK)
E Handbetrieb- Funktionstaste
F Schornsteinfeger-Funktionstaste
G Infotaste
H Reset Taste
I Betriebsarttaste Heizkreis(e)
L Display
M Betriebsarttaste Trinkwasser
A
Termékspecifikációk
Márka: | Elco |
Kategória: | Fűtési kazán |
Modell: | THISION L |
Szüksége van segítségre?
Ha segítségre van szüksége Elco THISION L, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek
Útmutatók Fűtési kazán Elco

19 Augusztus 2024

8 Augusztus 2024

30 Július 2024

16 Július 2024

11 Július 2024
Útmutatók Fűtési kazán
- Fűtési kazán Bosch
- Fűtési kazán Viessmann
- Fűtési kazán Atag
- Fűtési kazán Vaillant
- Fűtési kazán Atlantic
- Fűtési kazán Remeha
- Fűtési kazán Junkers
- Fűtési kazán Edilkamin
- Fűtési kazán ACV
- Fűtési kazán De Dietrich
- Fűtési kazán Nefit
- Fűtési kazán A.O. Smith
- Fűtési kazán Agpo Ferroli
- Fűtési kazán AGPO
- Fűtési kazán Artel
- Fűtési kazán Intergas
- Fűtési kazán Buderus
- Fűtési kazán Ferroli
- Fűtési kazán Saunier Duval
- Fűtési kazán TTulpe
- Fűtési kazán Bulex
- Fűtési kazán AWB
- Fűtési kazán Radson
- Fűtési kazán Daalderop
- Fűtési kazán Weishaupt
- Fűtési kazán Morco
- Fűtési kazán Brink
- Fűtési kazán Rendamax
- Fűtési kazán Oertli
- Fűtési kazán Unical
- Fűtési kazán Renova Bulex
- Fűtési kazán Benekov
- Fűtési kazán DrieOgas
- Fűtési kazán Worcester-Bosch
- Fűtési kazán Benraad
- Fűtési kazán Eco Heating Systems
- Fűtési kazán Brotje
- Fűtési kazán Nefit-Bosch
- Fűtési kazán Interdomo
- Fűtési kazán Atmos
- Fűtési kazán Schafer Heiztechnik
- Fűtési kazán Burnham
- Fűtési kazán Thermo Air
- Fűtési kazán ATTACK
- Fűtési kazán Bollaert Mazouttanks
- Fűtési kazán Chaffoteaux
- Fűtési kazán Coopra
Legújabb útmutatók Fűtési kazán

2 Április 2025

2 Április 2025

2 Április 2025

1 Április 2025

1 Április 2025

1 Április 2025

31 Március 2025

31 Március 2025

30 Március 2025

30 Március 2025