Customer Service: CS@panduit.com 800.777.3300 Technical Support: techsupport@panduit.com 866.405.6654 page 1
I N S T A L L A T I O N G U I D E
Temperature & Humidity Sensors
Temperature and humidity sensors are designed to add comprehensive
environmental monitoring to any iPDU.
Environmental sensors are engineered with an embedded microchip that
converts analog signals to digital format before data travels to the PDU,
providing greater data accuracy. This smart design also enables easy plug &
play installation that takes just moments to complete. Installation of the
sensors and ongoing equipment maintenance is further facilitated by the use
of the Quick Disconnect Coupler and Ethernet cable, which allow for the
convenient extension of sensors, movement of equipment, and an easy
disconnect method for removing rack enclosure doors.
Note: The Temperature and humidity Sensors are only designed to
connect to a G5 iPDU. Connecting it to another device may result in
damage.
SPECIFICATION
Electrical
Env Temp Sensor
(EA001)
ENV Temp, Humidity
Sensor (EB001)
Env 3- Temp, 1-
Humidity
Sensor (EC001)
Operational voltage
5V DC
Measuring Range
-10~ +65°C
-10~ +65°C, 10~90RH
Accuracy
±2° C
±2° C
±5% RH at 5- C 50°
10~90RH
Wire Type (From PDU to
sensor box)
CAT.5E Patch Cable, UTP
Length
2m
2m (from PDU to sensor
box)
1m (T1/ T3 Temp probe
to sensor box)
Maximum elevation,
Above MSL
0-10000 ft.
(o03048m)/0-50000 ft.
(0-15240m)
Temperature
(Operating/Storage)
0°C~+70°C (32 ~ 158°F)/-20~ + 70°C (-4 ~ 158°F)
Humidity
(Operating/Storage)
0 - 95%RH, non-condensing
Environmental Verication
ROHS, WEEE
Customer Service: CS@panduit.com 800.777.3300 Technical Support: techsupport@panduit.com 866.405.6654 page 2
I N S T A L L A T I O N G U I D E
SENSOR INVENTORY
INSTALLATION INSTRUCTIONS
The following instructions apply to both the temperature and the humidity sensors.
1. Secure the sensor box to the perforated rack enclosure door by threading a cable tie through the
recessed channel in the sensor box and through the door.
Note: There are two recessed channels on the back of the sensor box, which also includes a magnet to
help secure the sensor.
2. Secure the RJ45 cable along the desired path to the PDU using the remaining cable ties.
3. For the EC001 sensors only: Secure the two additional temperature probes near the top and the
bottom of the perforated rack enclosure door using the cable ties.
4. Use the RJ45 Quick Disconnect Coupler and an Ethernet cable to extend the length of the sensor input
cable and/or to serve as an easy disconnect point for rack door removal.
Note: Use either the 1.8m Ethernet cable included with the sensor or any other CAT5 or CAT6 Ethernet
cable with a standard RJ45 plug.
5. Plug the sensor cable (or the connected Ethernet cable) into the Sensor 1 or Sensor 2 port on the
PDU or the Sensor Hub (EF001 ).

Termékspecifikációk

Márka: Panduit
Kategória: nincs kategorizálva
Modell: EC001

Szüksége van segítségre?

Ha segítségre van szüksége Panduit EC001, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek




Útmutatók nincs kategorizálva Panduit

Panduit

Panduit FPONE4 Útmutató

1 Január 2025
Panduit

Panduit FPONE1 Útmutató

1 Január 2025
Panduit

Panduit FPONE3 Útmutató

1 Január 2025
Panduit

Panduit FPONE2 Útmutató

1 Január 2025
Panduit

Panduit MEHT187 Útmutató

30 December 2025
Panduit

Panduit EC001 Útmutató

30 December 2025
Panduit

Panduit PZICE Útmutató

15 December 2024
Panduit

Panduit PZICEA Útmutató

15 December 2024
Panduit

Panduit PZNDVK Útmutató

15 December 2024

Útmutatók nincs kategorizálva

Legújabb útmutatók nincs kategorizálva