Használati útmutató Emmeti CS11-U9132010-015

Emmeti Termosztát CS11-U9132010-015

Olvassa el alább 📖 a magyar nyelvű használati útmutatót Emmeti CS11-U9132010-015 (2 oldal) a Termosztát kategóriában. Ezt az útmutatót 4 ember találta hasznosnak és 2 felhasználó értékelte átlagosan 4.5 csillagra

Oldal 1/2
TAE S13 MC0 0MB 018080A1 140610


Suitable for 230 V~ or 24 V~ operation with switching load up to 5
(1) amps.
Red LED light shows when the thermostat is calling for heat.
Optional remote sensors - enables thermostat use in bathroom
applicatons.
Simple to use dial operation with clear temperature settings from 6 °C to 30 °C.
Wall mounted thermostat in elegant white design, only 85 mm wide x 85 mm high x 31 mm deep.
Accurate temperature control for maximum comfort - differential 0.5 °C.
Temperature range limiting stops to prevent accidental adjustment.
Compliant with directives EEC 89/336, 73/23 & 93/68 (CE)
6 Tannery Yard - Witney Street - Burford
Oxfordshire - OX18 4DW - UK
Phone: 01993 824900
Fax: 01993 824990
Email: sales@emmeti.co.uk
Website: www.emmeti.co.uk

1
~




.
Cable Aperture
38 mm
10 mm
43 mm
82 mm
60 mm
41 mm
82 mm




This electronic room thermostat (Fig. 1) is suitable
for reliable and accurate temperature regulation in
commercial and industrial premises as well as for
home installation.

When the measured room temperature is below the
value set on the dial the thermostat turns the relay
on and, at the same time, turns the red LED on for
’Heating’.

The user can set the room temperature by moving
the dial to any desired temperature between
6°C and 30°C, in one degree steps, against the
index mark next to the dial at the 9 o'clock position.


The thermostat should be positioned about 1.5m
from floor level and must avoid being positioned
near draughts, sources of heat or cold or direct
sunlight. To install the thermostat:
First remove the dial by inserting a small
screwdriver in the slot (2) and lifting the dial off
carefully.
Remove the front cover by disengaging the two
plastic teeth on the right hand side of the case
as shown in figs. 2 & 3.
The thermostat has been designed for fixed
wiring only. Cable access is through the rear of
the mounting backplate as shown in Fig. 4
The backplate can be secured either to a flat
vertical mounting surface or to a single gang flush
mounted wiring box: the fixing centres are shown in
Fig. 4
Fix the thermostat backplate to the wall through
the two screw holes with distance between
centres of 60 mm.
Make the wiring connections to the backplate as
shown in fig. 5 including any remote sensor
connections to terminals 6 and 7.
When the electrical connections are complete,
refit the cover by aligning the four plastic teeth
on the backplate with the holes in the cover and
then press gently to snap them together. Refit
the dial aligning the 'D' shape to the spindle.

It is possible to limit the rotation range for the dial
by following these steps:
First remove the dial by inserting a small
screwdriver in the slot (2) and lifting the dial off
carefully.
Pick up the plastic pins (4) parked to the left of
the knob area and set them (5) as shown in of
Fig. 6. In this example the rotation range (6) is
reduced to the angle shown.

When using the remote sensor option with the
thermostat, connect the sensor as shown in Fig. 5
() and remove the jumper on the bottom right hand
corner of the backplate - see fig. 7. Cased remote
sensors must be connected in cable of at least
1.5mm2cross sectional area and not greater than
25m in length. Do not put mains cables and sensor
cables next to one another.

Power supply:
U9 132 015: 230V~ -15% +10% 50Hz
U9 132 010: 24V~/= -15% +10% 50Hz
Power absorption: 1VA
Regulation range: 6°C .. 30°C
Sensor type: NTC 4,7k @ 25°C
internal
Remote sensor optional: U9 132 011
U9 132 012
Contact rating: 5 (1) A @ 250V~ SPDT
Protection grade: IP 30
Operating temperature: 0°C .. 40°C
Storage temperature: -10°C .. +50°C
Humidity limits: 20% .. 80% RH
(non condensing)
Case: Material: ABS self extinguishing V0
Color: Signal white (RAL 9003)
Size: 85 x 85 x 31 mm (W x H x D)
Weight: U9 132 015: ~135 gr.
U9 132 010: ~ 130 gr.
In view of the constant development of their products,
the manufacturer reserves the right to change technical
data and features without prior notice. The consumer is
guaranteed against any lack of conformity in accordance
with the European Directive 1999/44/EC as well as the
manufacturer’s own warranty policy. The full text of the
warranty is available on request from Emmeti UK Ltd.
TAE S13 MC0 0MB 018080A1 140610
2
TAE S13 MC0 0MB 018080A1 140610


Suitable for 230 V~ or 24 V~ operation with switching load up to 5
(1) amps.
Red LED light shows when the thermostat is calling for heat.
Optional remote sensors - enables thermostat use in bathroom
applicatons.
Simple to use dial operation with clear temperature settings from 6 °C to 30 °C.
Wall mounted thermostat in elegant white design, only 85 mm wide x 85 mm high x 31 mm deep.
Accurate temperature control for maximum comfort - differential 0.5 °C.
Temperature range limiting stops to prevent accidental adjustment.
Compliant with directives EEC 89/336, 73/23 & 93/68 (CE)
6 Tannery Yard - Witney Street - Burford
Oxfordshire - OX18 4DW - UK
Phone: 01993 824900
Fax: 01993 824990
Email: sales@emmeti.co.uk
Website: www.emmeti.co.uk

1
~




.
Cable Aperture
38 mm
10 mm
43 mm
82 mm
60 mm
41 mm
82 mm




This electronic room thermostat (Fig. 1) is suitable
for reliable and accurate temperature regulation in
commercial and industrial premises as well as for
home installation.

When the measured room temperature is below the
value set on the dial the thermostat turns the relay
on and, at the same time, turns the red LED on for
’Heating’.

The user can set the room temperature by moving
the dial to any desired temperature between
6°C and 30°C, in one degree steps, against the
index mark next to the dial at the 9 o'clock position.


The thermostat should be positioned about 1.5m
from floor level and must avoid being positioned
near draughts, sources of heat or cold or direct
sunlight. To install the thermostat:
First remove the dial by inserting a small
screwdriver in the slot (2) and lifting the dial off
carefully.
Remove the front cover by disengaging the two
plastic teeth on the right hand side of the case
as shown in figs. 2 & 3.
The thermostat has been designed for fixed
wiring only. Cable access is through the rear of
the mounting backplate as shown in Fig. 4
The backplate can be secured either to a flat
vertical mounting surface or to a single gang flush
mounted wiring box: the fixing centres are shown in
Fig. 4
Fix the thermostat backplate to the wall through
the two screw holes with distance between
centres of 60 mm.
Make the wiring connections to the backplate as
shown in fig. 5 including any remote sensor
connections to terminals 6 and 7.
When the electrical connections are complete,
refit the cover by aligning the four plastic teeth
on the backplate with the holes in the cover and
then press gently to snap them together. Refit
the dial aligning the 'D' shape to the spindle.

It is possible to limit the rotation range for the dial
by following these steps:
First remove the dial by inserting a small
screwdriver in the slot (2) and lifting the dial off
carefully.
Pick up the plastic pins (4) parked to the left of
the knob area and set them (5) as shown in of
Fig. 6. In this example the rotation range (6) is
reduced to the angle shown.

When using the remote sensor option with the
thermostat, connect the sensor as shown in Fig. 5
() and remove the jumper on the bottom right hand
corner of the backplate - see fig. 7. Cased remote
sensors must be connected in cable of at least
1.5mm2cross sectional area and not greater than
25m in length. Do not put mains cables and sensor
cables next to one another.

Power supply:
U9 132 015: 230V~ -15% +10% 50Hz
U9 132 010: 24V~/= -15% +10% 50Hz
Power absorption: 1VA
Regulation range: 6°C .. 30°C
Sensor type: NTC 4,7k @ 25°C
internal
Remote sensor optional: U9 132 011
U9 132 012
Contact rating: 5 (1) A @ 250V~ SPDT
Protection grade: IP 30
Operating temperature: 0°C .. 40°C
Storage temperature: -10°C .. +50°C
Humidity limits: 20% .. 80% RH
(non condensing)
Case: Material: ABS self extinguishing V0
Color: Signal white (RAL 9003)
Size: 85 x 85 x 31 mm (W x H x D)
Weight: U9 132 015: ~135 gr.
U9 132 010: ~ 130 gr.
In view of the constant development of their products,
the manufacturer reserves the right to change technical
data and features without prior notice. The consumer is
guaranteed against any lack of conformity in accordance
with the European Directive 1999/44/EC as well as the
manufacturer’s own warranty policy. The full text of the
warranty is available on request from Emmeti UK Ltd.
TAE S13 MC0 0MB 018080A1 140610
2

Termékspecifikációk

Márka: Emmeti
Kategória: Termosztát
Modell: CS11-U9132010-015

Szüksége van segítségre?

Ha segítségre van szüksége Emmeti CS11-U9132010-015, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek




Útmutatók Termosztát Emmeti

Útmutatók Termosztát

Legújabb útmutatók Termosztát