WARNING CAUTION
Read through this Installation Manual before installing.
WARNING
Installer must apply for standard installation guidance.
• Please perform the installation work, select insulation, and perform heat insulation construction in accordance with
the laws and regulations of each country.
• For specifications of connection piping, refer to Table 1 below.
• Piping is limited to newly installed piping.
Even with newly installed piping, remove places to which brazing material is adhered, or which have been burnt the burner.by
• Please keep minimum wall thickness of the pipe for installation.
• Do not disassemble the GAS TIGHT JOINT.
• When rk working in high places, wo must be performed with a stable scaffold.
• Carry out the work of connecting the GAS TIGHT JOINT one location at a time making sure each location is secure.,
(Do not perform simultaneous work on 2 or more locations between the same outdoor and indoor unit)
• Do not use the GAS TIGHT JOINT which has been dropped.
•
The GAS TIGHT JOINT cannot be re-used if it has already been inserted into the piping, temporarily fixed, and removed.
•
Do not turn the nut in the loosening direction.
INSTALLATION MANUAL
SDGTB06·09·12·15·19·22·28
SDGTB0906·1209·1512·1915·2219·2522·2825·3428
BDGTA34·41, SDGTLB22·28
3V022006-1A
GAS TIGHT JOINT The case which may cause
dangerous situation such as
death or severe injury, at the
same time, it may cause
property damage when
mis-operated.
The case which may cause
dangerous situation such as
injury or minor injury, at the
same time, it may cause
property damage when
mis-operated.
R410A, R32 UNIT ONLY
Removing the thermal insulation
material (copper pipe)
1
1) Be careful not to damage the pipe.
2) If using insulated copper pipe, cut in a
cylindrical direction, not in a lengthwise
direction.
(Cylindrical direction)
(Lengthwise direction)
R32: Type BDGTA34/41 are not applicable in the EU
Table 1 : Specication of connection piping Standard
ASTM B280 ASTM B88 (Type L) EN12735
Model name Size (O.D.) O60 H58 Thickness (mm) O60
O50 H58 R220 R250 R290Thickness (mm) Thickness (mm)
Same diameter Different diameter
SDGTB06
SDGTB0906
–φ6.35 –0.762±0.08 – – – – – 0.80±0.08
1.00±0.13
SDGTB09
SDGTB1209
φ9.52 – 0.813±0.08 – 0.762±0.08 – 0.80±0.08
– – 1.00±0.13
SDGTB12
SDGTB1512
φ12.7 –0.813±0.08 –0.889±0.11
– – 0.80±0.08
––0.91±0.09
– 1.00±0.13
SDGTB15
SDGTB1915
φ15.88 –0.889±0.11 –1.016±0.11 ––0.91±0.09
–1.00±0.13
SDGTB19
SDGTB2219
φ19.05 –1.07±0.10 – 1.07±0.11 –1.00±0.13
–– 1.25±0.19
SDGTB22
SDGTLB22 SDGTB2522 φ22.22 –1.14±0.10 –1.14±0.11
– – 1.00±0.13
––1.25±0.19
1.63±0.25
–
SDGTB2825
φ25.4 *2 – – – – – – – – 1.00±0.13
SDGTB28
SDGTLB28 SDGTB3428
φ28.58 –1.27±0.10 –1.27±0.13 – 1.00±0.13
1.25±0.19
––1.63±0.25
BDGTA34 – φ34.92 – 1.40±0.15 – 1.40±0.15 – 1.25±0.19
––1.63±0.25
BDGTA41 – – φ41.28 –1.52±0.15 –1.52±0.15 – 1.25±0.19
– – 1.63±0.25
Notes) 1. “–” : No settings
2. *2 : For connection to the stop valve outlet pipe only.

Bend, Kink
Cut off Scratches
Half of pipe thickness
chamfering is
recommended
Copper Pipe
CAUTION
Insufficient insertion
Nut
Pipe Joint main body
Incore
Burr of pipe inside
Check the pipe appearance Cut the tube to length
2 3
The acceptable limit of pipe bend and ality is that pipe can be inserted to the GAS TIGHT JOINT without ov force.
1) If there are scratches, bends, kinks, ovals or thermal aging at the insert part, cut them off.
2) If there are foreign objects, oil, burrs inside and outside of the pipe, remove them.
3)
If connecting pipes are covered with oxide films, remove them by a fine sand paper. Do not polish too much.
4) For the piping minimum insertion allowance dimension and the maximum long axis side
dimension for piping which has been slightly flattened, be sure to follow the dimensions in Table 2.
CAUTION Never scratch pipe sections horizontally, as they may cause refrigerant leakage.
• Cut the pipe slowly to avoid pipe
deformation.
• If the rotary tube cutter is
damaged or dirty, clean it before
use.
Pipe insertion
6
•
Insertion the pipe straight.
1) Insert firmly by hand until the pipe stops.
2)
Make sure that the insertion standard line is no longer visible.
Chamfering of the pipe
Marking the insertion standard line
5
4
Mark the insertion “T” or “L” standard
line with the marking gauge and
marker pen at proper position of
each pipe size.
1) Outside chamfering / Chamfer about 0.5 C
2) Inside chamfering / Deburr the inner part
•
If no chamfering of the outside of the pipe is performed,
the O-ring would be damaged and cause leakage.
•
Chamfer the inside to ensure a proper refrigerant flow
rate. The 12.7 pipe contains an Incore.
If chamfering of the inside is insufficient, it may cause
improper insertion or damage to the internal struc-
ture, so be sure to carry out chamfering of the inside.
Outside chamfering
Marking method using marking gauge:
Table 2 : Minimum insertion allowance and maximum long axis side dimension for piping
6.35
9.52
12.7
15.88
19.05
22.22
25.4
28.58
34.92
41.28
20.9
22.3
23.9
36.4
37.7
41.2
42.2
43.5
48.9
49.9
6.45
9.67
12.85
16.03
19.18
22.32
25.51
28.69
34.99
41.36
SIZE
(O.D.)
A. Piping minimum
insertion (mm) B. Maximum diameter (mm)
A
B
GAS TIGHT
JOINT
1) Use a rotary tube cutter.
2) Ensure that the tube is cut square.
3) Check the pipe has retained its shape
and is damage free.
•
Do not tighten the nut before pipe insertion.
•
When inserting the pipe, do not apply excessive force.
The O-ring will be damaged.
•
Do not pull out the tube once it has been inserted.
There is a risk of refrigerant leakage due to damage to
the pipe, damage to the packing or damage to the
incore of
12.7 joint.
•
Carry out chamfering with the pipe pointing
downward, in order to prevent foreign objects from
entering the pipe.
In case any foreign objects enter the pipe, remove them.

Monkey wrench
Complete tightening
the nut until the green
indicator disappears.
Nut part
Main body
WARNING
CAUTION
Checking
Tightening of nut 98
Hold the main body and tighten the nut with a monkey
wrench to the direction of arrow until the green indicator
disappears and the nut comes into contact with the flat face
of the body.
• In case of insufficient nut tightening,
it may cause pipes to come off.
• Excessive tightening prohibited.
It may cause joint damage or stress
corrosion cracking.
Tighten the nut completely using the
same level of torque as the level which
is sufficient to overcome the pawls.
• Before using the tools, be sure you
understand how to use them correctly.
• Do not turn the nut in the loosening
direction.
• Do not tighten the joint main body.
1) Green indicator should be hidden.
2) Place the marking gauge on the end face of the nut and make sure that
the “T” or “L” shaped mark falls completely within the notch in the
marking gauge.
The marking gauge contains one notch for measuring the insertion of
pipe of 28 or less, and another notch for measuring the insertion of
pipe of 31 or more. Be sure you are using the correct notch when
measuring.
If the “T” or “L” shaped mark falls outside the notch in the marking gauge,
cut off the joint, replace it with a new joint, and carry out construction
again.
Manual tightening of nut
7
Hold the main body and tighten the nut in the
direction of the arrow hand until it will not turn by
anymore.
Cautions after construction
10
[Example of work that requires caution]
1) If connecting REFNET joints
• After tightening, do not rotate the joint excessively.
• Do not apply excessive twisting forces to the GAS TIGHT JOINT after connection.
• First, connect the GAS TIGHT JOINT to the joint, adjust the orientation of the
joint, then carry out connection to the pipe.
Green indicator
* Install the joint so that it branches
on a horizontal plane.
• If connection of the joint is carried out after connection with the pipe, when the GAS TIGHT JOINT is tightened,
the joint will turn along with it, so it may be difficult to construct on a horizontal plane.
• Before insulating, check according to step Checking.
9
Termékspecifikációk
Márka: | Daikin |
Kategória: | Kazánok és kazánok |
Modell: | SDGTB06 |
Szüksége van segítségre?
Ha segítségre van szüksége Daikin SDGTB06, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek
Útmutatók Kazánok és kazánok Daikin

9 Április 2025

9 Április 2025

9 Április 2025

10 Január 2025

10 Január 2025

10 Január 2025

10 Január 2025

10 Január 2025

10 Január 2025

10 Január 2025
Útmutatók Kazánok és kazánok
- Kazánok és kazánok Beko
- Kazánok és kazánok Dometic
- Kazánok és kazánok Electrolux
- Kazánok és kazánok Whirlpool
- Kazánok és kazánok Ariston Thermo
- Kazánok és kazánok Philips
- Kazánok és kazánok Gorenje
- Kazánok és kazánok Adler
- Kazánok és kazánok Bosch
- Kazánok és kazánok Panasonic
- Kazánok és kazánok AEG
- Kazánok és kazánok Teka
- Kazánok és kazánok Hisense
- Kazánok és kazánok Siemens
- Kazánok és kazánok Corbero
- Kazánok és kazánok Camry
- Kazánok és kazánok Cointra
- Kazánok és kazánok Viessmann
- Kazánok és kazánok Infiniton
- Kazánok és kazánok VOX
- Kazánok és kazánok Fagor
- Kazánok és kazánok Rommelsbacher
- Kazánok és kazánok Jocel
- Kazánok és kazánok Hotpoint
- Kazánok és kazánok Haier
- Kazánok és kazánok Sencor
- Kazánok és kazánok Qlima
- Kazánok és kazánok Baxi
- Kazánok és kazánok CATA
- Kazánok és kazánok Hitachi
- Kazánok és kazánok Inventum
- Kazánok és kazánok Kospel
- Kazánok és kazánok Eta
- Kazánok és kazánok Atag
- Kazánok és kazánok Solac
- Kazánok és kazánok Stiebel Eltron
- Kazánok és kazánok Mora
- Kazánok és kazánok Vaillant
- Kazánok és kazánok Orbegozo
- Kazánok és kazánok Respekta
- Kazánok és kazánok GE
- Kazánok és kazánok Guzzanti
- Kazánok és kazánok Concept
- Kazánok és kazánok SVAN
- Kazánok és kazánok Rommer
- Kazánok és kazánok Atlantic
- Kazánok és kazánok SolarEdge
- Kazánok és kazánok Midea
- Kazánok és kazánok Truma
- Kazánok és kazánok Remeha
- Kazánok és kazánok Dimplex
- Kazánok és kazánok Aspes
- Kazánok és kazánok Tesy
- Kazánok és kazánok HTW
- Kazánok és kazánok Taurus
- Kazánok és kazánok Junkers
- Kazánok és kazánok Technika
- Kazánok és kazánok Quantum
- Kazánok és kazánok Franke
- Kazánok és kazánok Rinnai
- Kazánok és kazánok Edilkamin
- Kazánok és kazánok ACV
- Kazánok és kazánok De Dietrich
- Kazánok és kazánok Arçelik
- Kazánok és kazánok AquaTech
- Kazánok és kazánok Nefit
- Kazánok és kazánok A.O. Smith
- Kazánok és kazánok Easypix
- Kazánok és kazánok Intergas
- Kazánok és kazánok Eldom
- Kazánok és kazánok Buderus
- Kazánok és kazánok Elco
- Kazánok és kazánok Masterwatt
- Kazánok és kazánok Nibe
- Kazánok és kazánok Ferroli
- Kazánok és kazánok Elba
- Kazánok és kazánok Kelvinator
- Kazánok és kazánok Buffalo
- Kazánok és kazánok TTulpe
- Kazánok és kazánok Worcester
- Kazánok és kazánok Plieger
- Kazánok és kazánok Bulex
- Kazánok és kazánok Waeco
- Kazánok és kazánok AWB
- Kazánok és kazánok Quooker
- Kazánok és kazánok OSO
- Kazánok és kazánok Kunft
- Kazánok és kazánok La Nordica
- Kazánok és kazánok Clage
- Kazánok és kazánok Noveen
- Kazánok és kazánok Joven
- Kazánok és kazánok Daalderop
- Kazánok és kazánok Fakir
- Kazánok és kazánok Eccotemp
- Kazánok és kazánok Biasi
- Kazánok és kazánok Morco
- Kazánok és kazánok Thermor
- Kazánok és kazánok Sentry
- Kazánok és kazánok Country Comfort
- Kazánok és kazánok Keston
- Kazánok és kazánok Burco
- Kazánok és kazánok LEMET
- Kazánok és kazánok Duwaco
- Kazánok és kazánok Wesen
- Kazánok és kazánok Rheinstrom
- Kazánok és kazánok Wagaparts
- Kazánok és kazánok IQE
- Kazánok és kazánok Khind
- Kazánok és kazánok Wahlbach
- Kazánok és kazánok LERAN
- Kazánok és kazánok Ygnis
- Kazánok és kazánok Dux
- Kazánok és kazánok Intellihot
- Kazánok és kazánok Wijas
- Kazánok és kazánok Airthereal
- Kazánok és kazánok Thermoflow
- Kazánok és kazánok IStore
- Kazánok és kazánok Apricus
- Kazánok és kazánok Aquamarin
- Kazánok és kazánok Sime
- Kazánok és kazánok Hydrotherm
- Kazánok és kazánok Amtrol
- Kazánok és kazánok Neopower
- Kazánok és kazánok Gleamous
- Kazánok és kazánok AquaMAX
- Kazánok és kazánok My-PV
- Kazánok és kazánok EvoHeat
- Kazánok és kazánok Rheem
- Kazánok és kazánok Mission Air
- Kazánok és kazánok Solahart
- Kazánok és kazánok ENEFT
- Kazánok és kazánok Imarflex
- Kazánok és kazánok MicroHeat
- Kazánok és kazánok Noritz
- Kazánok és kazánok BTI Aqua-Solutions
Legújabb útmutatók Kazánok és kazánok

1 Április 2025

31 Március 2025

13 Január 2025

13 Január 2025

13 Január 2025

12 Január 2025

9 Január 2025

5 Január 2025

5 Január 2025

5 Január 2025