Installation Instructions
Welding adapter
G1 / G¾
706013/02 08/2017
UK
UK
UK
UK
UK
2
A
BB
1 2
A: Groove for the O-ring (E30072 only); B: Marking for alignment
Order no. Type Material Pressure rating *
E30009 G¾ - Ø 50mm stainless steel (316S12) 25 bar
E30013 G1 - Ø 50mm stainless steel (316S12) 150 bar
E30060 G1 - Ø 50mm steel (1.0570) 50 bar
E30072 G1 - Ø 50mm stainless steel (316S12) 150 bar
* for the connection sensor - adapter
E30072 is supplied with a Viton O-ring and an EPDM O-ring
Note
The welding operation must be carried out by authorised personnel.
It must be carried out carefully and according to state-of-the-art technology.
During welding and the following cooling phase, neither sensor nor O-ring must
be in place.
The surfaces must be free from soiling of any kind.
Welding tools must be suitable for the adapter and wall material.
Preparations
Bore a hole in the pipe or housing wall with the outside diameter of the adapter
(max. oversize: 0.2 mm).
If possible, screw a welding mandrel into the adapter
(order no. E30435 for G1 thread, order no. E30071 for G3/4 thread).
3
UK
Welding operation
3 4
Align the adapter: Turn the marking to the position provided for the connector /
display of the screwed sensor (see figure 2).
Fix the adapter at several points with sufficient holding force, apply the fixing
points at equal distance opposite each other (see figure 3).
Apply the welding seams between the fixing points opposite each other (see
figure 4). Ensure sufficient intervals between the individual sections (cooling
phases to avoid glowing through / warping of the adapter due to overheating).
The power of the welding device must be adapted to the thickness of the wall.
After welding
Let the adapter cool down.
Clean the thread from welding residues.
Grease the thread with lubricating paste.
The paste must be suitable and approved for the application and compatible
with the elastomers used.
For the adapter E30072, place one of the supplied O-rings in the groove of the
adapter (Viton or EPDM O-ring, depending on the fluid). It must snap flush into
the groove over its whole circumference (see figure 1).
Note: If the sensor can only be screwed into the thread with great resistance,
apply no force.
If it is not possible to rectify the thread, remove the adapter and weld in a new one.

Termékspecifikációk

Márka: IFM
Kategória: nincs kategorizálva
Modell: E30072

Szüksége van segítségre?

Ha segítségre van szüksége IFM E30072, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek




Útmutatók nincs kategorizálva IFM

IFM

IFM PE2599 Útmutató

23 Március 2025
IFM

IFM MK5312 Útmutató

23 Március 2025
IFM

IFM RU6035 Útmutató

18 Március 2025
IFM

IFM SF3210 Útmutató

18 Március 2025
IFM

IFM RU6045 Útmutató

18 Március 2025
IFM

IFM KI0200 Útmutató

18 Március 2025
IFM

IFM PT2400 Útmutató

16 Január 2025
IFM

IFM O2D532 Útmutató

16 Január 2025
IFM

IFM PA3027 Útmutató

16 Január 2025
IFM

IFM TW2001 Útmutató

14 Január 2025

Útmutatók nincs kategorizálva

Legújabb útmutatók nincs kategorizálva