3
GM1001 Rack PDU Manual
3Table Of Contents
© 2018 Geist
Table of Contents
Introduction 5
.............................................................................................................................. 5Welcome
About this Manual 8
.................................................................................................................... 8Revision History
.................................................................................................. 8Organization of the Manual
................................................................................................................... 8Audience Profile
......................................................................................................... 8On-line Documentation
................................................................................................... 9Reporting Document Errors
.......................................................................................................................... 9Conventions
.......................................................................................................................................................... 9Softw are
.......................................................................................................................................................... 9Hardw are
.......................................................................................................................................................... 11Safe ty
.......................................................................................................................................................... 12Figure s
.......................................................................................................................................................... 12Tables
Chapter 1 - Product Specifications 13
............................................................................................................................. 13Overview
..................................................................................................................... 13Environmental
......................................................................................................................................................... 13Temperature
.......................................................................................................................................................... 13Humidity
.......................................................................................................................................................... 13Elevation
............................................................................................................................. 13Electrical
............................................................................................................................................... 14Re ce ptacle Ratings
...................................................................................................... 14Regulatory Compliance
........................................................................................................................ 14Unde rwr iters Laboratories (UL)
................................................................................................ 14Federal Com munications Com mission (FCC)
Chapter 2 - Installation 15
.................................................................................................................... 15Pre-Installation
.......................................................................................................................... 16Installation
.......................................................................................................................................................... 16Mounting
Chapter 3 - Optional Surge Suppression 24
......................................................................................... 24Surge Protection Circuit Ratings
Chapter 4 - Optional Local Metering 25
....................................................................................................................... 25Power Meter
...................................................................................................................... 25Current Meter
Rack PDU Manual
GM1001 Rack PDU Manual
4
© 2018 Geist
Service/Tech Support 26
................................................................................................... 26Service and Maintenance
...................................................................................................... 26More Technical Support
Introduction 5
© 2018 Geist
GM1001
Introduction
Welcome
Notice to Users
Geist, a division of Vertiv, Inc., reserves the right to make changes to this document
without notice to any user or reseller of this product. Geist, a division of Vertiv, Inc.,
also reserves the right to substitute or terminate distribution of this document, with no
obligation to notify any person or party of such substitutions or terminations.
Copyrights
© 2018 - Geist, a division of Vertiv, Inc. All Rights Reserved.
Trademarks
All Trademarks contained herein are registered to Geist, a division of Vertiv, Inc.
Use and Disclosure Restrictions
The software and documentation contained in this publication are copyrighted materials.
Recovery Act Buy American
Geist products adhere to the Buy American provisions of the American Recovery and
Reinvestment Act of 2009 (Recovery Act). All Geist goods manufactured in our Lincoln,
Nebraska, plant have undergone substantial transformation during production.
Trade Agreements Act (TAA)
Geist goods manufactured in our Lincoln, Nebraska, plant have undergone substantial
transformation during production. These Geist products adhere to U.S. Trade
Agreements Act and can be supplied for GSA Schedules and other government
contracts.
Rack PDU Manual6
© 2018 Geist
GM1001
Geist Policy on Conict Minerals
This document details Geist’s corporate policy regarding the use of conict minerals.
The policy expressed in this document should be considered to cover the Geist and
Geist Europe divisions of Vertiv Inc.
Section 1502 of the Dodd-Frank Act which was passed by the US Congress in 2010
requires certain companies to annually disclose their use of conict minerals. Conict
minerals covered under this act include tantalum, tin, tungsten, and gold.
Although Geist is not directly subjected to the requirements of the Dodd-Frank Act,
Geist recognizes that all companies within the electronics manufacturing industry
supply chain are impacted by this legislation. Geist supports the intent of the law,
which is the reduction of violence within the Democratic Republic of the Congo and will
take several actions to both advance the goals of the Dodd-Frank Act and to provide
exceptional support to our customers.
· Geist will work with our direct suppliers to identify purchased components and
materials that contain tin, tantalum, tungsten or gold.
· Geist will work with our direct suppliers to trace sources of any tin, tantalum,
tungsten or gold used in our products back to the smelter.
· Geist will document our efforts to trace tin, tantalum, tungsten, and gold minerals
back to the smelter and will accurately report the results to our customers.
· Geist will continue to monitor industry progress in identifying conict-free smelters
and will adjust corporate policy as the electronics supply chain becomes more fully
documented.
Geist will not require that our direct suppliers source only conict-free minerals until an
adequate number of smelters has been reliably identied and audited by The Electronic
Industry Citizenship Coalition (EICC) and the Global e-Sustainability Initiative (GeSI) to
service the electronic industry supply chain. Mandating a conict-free supply chain
before an adequate number of smelters has been identied will prohibit the use of all
tin, tantalum, tungsten, and gold originating in the Democratic Republic of the Congo
and surrounding countries. This prohibition would cut off the sole income source for
many artisanal miners within the region and may result in increased violence within the
Democratic Republic of the Congo in direct opposition to the goals of the Dodd-Frank
Act. Geist will work continuously with our direct suppliers in order to annually increase
the percentage of documented conict-free minerals that are used in our products until
all products can be certied as conict-free.
Introduction 7
© 2018 Geist
GM1001
WEEE Declaration
Geist Europe is obligated to nance the cost of the collection, treatment, recovery and
environmentally sound disposal of all products sold by Geist Europe into the UK market
this includes:
· New WEEE (displaying the crossed out wheeled bin symbol’) that Geist Europe has
placed onto the market after the 13th August 2005; and
· Historic WEEE (not displaying the crossed out wheeled bin symbol), when Geist
Europe is supplying new WEEE that is intended to replace the historic WEEE and is
of equivalent type or fullls the same function even if the historic WEEE was
manufactured by a third party.
Please contact Geist Europe on 01823 275100 for further details or to arrange collection.
(UK Only)
Document Usage
All reasonable efforts have been made to assure the accuracy of this document from
any technical or typographical errors or omissions. Geist, a division of Vertiv, Inc., and
its affiliates disclaim responsibility for any labor, materials, or costs incurred as a result
of usage of this document. Nor shall Geist, a division of Vertiv, Inc., and its afliates be
liable for any damages, inclusive of loss of prots or data, arising from the use of or in
connection with this document.
Geist, a division of Vertiv, Inc., reserves the right to make changes to this document
without notice to any user or reseller of this product. Geist, a division of Vertiv, Inc.,
also reserves the right to substitute or terminate distribution of this document, with no
obligation to notify any person or party of such substitutions or terminations.
Rack PDU Manual8
© 2018 Geist
GM1001
About this Manual
This document provides an overview of Geist product(s), the major topics covered include:
· Copyright, Trademarks, and Disclosure Restrictions.
· Instructions for installing, powering and using the equipment.
· Information that will aid in managing and maintaining the equipment.
Revision History
Revision
Date
Notes
Approved By
1.0
3/2/2017
Original Published Version
JLP
2.0
6/27/2017
Changed logo, email, and website
QTN
3.0
6/30/2017
Updated Information and Format
JB
3.1
5/15/2018
Updated Receptacle table, Vertiv info.
JB
Organization of the Manual
This Geist document contains the following product information:
·Product Specications - This chapter describes the major product characteristics and its
functional role within the system. Where appropriate, reference to cabling among product
components and to other Geist product(s) is provided.
·Installation - This chapter provides installation information for the preparation and use of
Geist products as well as procedures required to adequately mechanically and
electrically attach Geist product into supporting systems.
·Optional Surge Suppression - This chapter provides information on the surge
suppression circuits in specied models.
·Optional Local Metering - This chapter provides information on Local Metering options for
specific models.
Audience Profile
This document is intended for use by authorized technicians experienced with same of
similar product types and for personnel requiring guidance for equipment installation,
operation, maintenance, and support.
On-line Documentation
This document is available on-line and within the corresponding
Geist Product Manuals
.
Additional Geist product supporting
Videos
,
Product Literature
and
Case Studies
can be
found on the
Geist Resource
page.
About this Manual 9
© 2018 Geist
GM1001
Product rmware updates can be found and downloaded from the
Geist Support
site, under
Firmware Updates
.
Should this product fail within its warranty period and be in need of repair or replacement, a
Return Material Authorization may be obtained on-line from the
RMA Form
link located within
the
Geist Support
site.
Reporting Document Errors
Should you discover any error or identify a deciency in this document, please take time to
contact us at the following email address:
Geist-Documents@geistglobal.com
Please be sure to provide us with the document name, part number, and page number(s).
Also, please provide us with description of the error or the deficiency for the document. If
you would like for us to contact you, please provide us with your name and contact
information.
Thank you for your time. We appreciate any comments and feedback you can provide.
Conventions
The information contained within this document is established around the framework of
various conventions, which are defined as follows:
Software
·Release Management: Product name, Version control ; (GU V 3.0.0)
oProduct Name: Name of Hardware Platform
oVersion control: V(ersion) Platform #, Major #, Minor #
Hardware
Product Classication
oPower Distribution Unit
§Basic
§Monitored only
§Switched only
§Monitored + Switched
oEnvironmental Monitoring
oCooling
oData Center Infrastructure Management (DCIM)
Rack PDU Manual10
© 2018 Geist
GM1001
Figure 1 Overlay Symbology Guide
Figure 1
The chart above depicts the symbols used on Geist overlays.
Rack PDU Manual12
© 2018 Geist
GM1001
Figures
Figures presented in this document are identied and designated as
follows:
'Figure:', Chapter # - Image #
Example:
Figure 1-1 Name and/or Title goes here
Tables
Tables presented in this document are identied and designated as follows:
'Table:', Chapter # - Image #
Example:
Table 1-1 Name and/or Title goes here
Column 1
Column 2
Column 3
Column 4
Column 5
Text
Text
Text
Text
Text
Text
Text
Text
Text
Text
Text
Text
Text
Text
Text
Text
Text
Text
Text
Text
About this Manual 13
© 2018 Geist
GM1001
Chapter 1 - Product Specifications
Overview
The BR, SP, SVR, VRT, NSV, and VSS Series products are Power Distribution Units (PDU) intended
for connection to a 15 or 20 Amp AC Mains circuit. The PDUs may include optional single pole
thermal breakers for supplementary over-current protection of the output receptacles. The VRT,
SVR, NSV, and VSS Series are available in vertical congurations rated 125 V, while the BR and SP
Series are available in horizontal configurations rated 125 V. All PDU Series covered by this
instruction sheet can optionally be congured with a Geist Power Meter that provides local
monitoring and display of Current, Voltage, Wattage, and Power Factor.
Environmental
Temperature
Table 1-1 Temperature Limits
Minimum
Maximum
Operating
10°C (50°F)
45°C (113°F)
Storage
-25°C (13°F)
65°C (149°F)
Humidity
Table 1-2 Humidity Limits
Minimum
Maximum
Operating
5%
95% (non-condensing)
Storage
5%
95% (non-condensing)
Elevation
Table 1-3 Elevation Limits
Minimum
Maximum
Operating
0 m (0 ft)
3,050 m (10,000 ft)
Storage
0 m (0 ft)
15,240 m (50,000 ft)
Electrical
Electrical product characteristics an performance are dened below. Also, please see the
product nameplate for additional rating limits.
Rack PDU Manual14
© 2018 Geist
GM1001
Receptacle Ratings
Table 1-4 Receptacle Ratings
Type
Ratings
NEMA 5-15R or L5-15R
125Vac, 12A
NEMA 5-20R or L5-20R
125Vac, 16A
Regulatory Compliance
Geist products are regulated for Safety, Emissions, and Environment Impact per the below agencies
and policies.
Underwriters Laboratories (UL)
UL Standards are used to assess products; test components, materials, systems and performance;
and evaluate environmentally sustainable products, renewable energies, food and water products,
recycling systems and other innovative technologies.
The UL standards specic to this equipment are as noted on the device nameplate.
Federal Communications Commission (FCC)
The Federal Communications Commission (FCC) regulates interstate and international communications
by radio, television, wire, satellite, and cable in all 50 states, the District of Columbia and U.S.
territories. An independent U.S. government agency overseen by Congress, the commission is the
United States' primary authority for communications laws, regulation and technological innovation.
The FCC standards specific to this equipment are:
This Class A device complies with part 15 of the FCC Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
WARNING
Changes or modications to this unit not expressly approved by the party
responsible for compliance could void the user’s authority to operate this
equipment.
Chapter 2 - Installation 15
© 2018 Geist
GM1001
Chapter 2 - Installation
Pre-Installation
·Install the PDU such that the amount of airow required for safe operation of equipment is not
compromised.
·Mount the PDU so that a hazardous condition is not achieved due to uneven mechanical
loading.
·Follow nameplate ratings when connecting equipment to the branch circuit. Take into
consideration the effect that overloading of the circuits might have on overcurrent protection
and supplied wiring.
·The PDU relies on the building installation for protection from overcurrent. A certied
overcurrent protection device is required in the building installation. The overcurrent protection
device should be sized according to the PDUs nameplate ratings and local/national electrical
code.
·Reliable earthing of rack-mount equipment should be maintained. Particular attention should
be given to supply connections other than direct connections to the branch circuit. The PDU
must be connected to an earthed socket outlet.
·PDU is intended for restricted-access locations. Only qualied service personnel should
install and access the PDU.
·For pluggable equipment, install the PDU so the input plug or appliance coupler may be
disconnected for service.
·The PDU is intended for indoor use only. Do not install the unit in wet or outdoor
environments, and do not install it next to water tanks or plumbing.
·The PDU is intended for use with TN, TT, or IT power supply systems.
Chapter 2 - Installation 17
© 2018 Geist
GM1001
Figure 2-2 Mini L Brackets
Mini "L" Brackets (SLB-4)
Using the mini L” brackets, attach PDU to rack as shown.
Figure 2-3 Vertical Extension Brackets
Vertical Extension Brackets (VCB-1)
Using the vertical extension brackets, attach PDU to rack as shown.
Rack PDU Manual18
© 2018 Geist
GM1001
Figure 2-4 Toolless Mounting Hardware
Toolless Mounting Hardware (11621)
Secure toolless mounting buttons to PDU as shown. Use toolless buttons with key-holed slots built
into cabinet or with optional Geist key-holed brackets.
Figure 2-5 Toolless Full Length Brackets
Toolless Full Length Bracket (TLFL)
Using full length toolless bracket and toolless mounting buttons, attach PDU to rack as shown.
Chapter 2 - Installation 19
© 2018 Geist
GM1001
Figure 2-6 Single Side Mount 2 Units Brackets
Single Side Mount Two Unit Brackets (TSMX2)
Using single side mount two unit brackets and toolless mounting buttons, attach PDU to rack as
shown.
Figure 2-7 Offset/Side Mount Brackets
Offset/Side Mount Brackets (EZB-1)
Using the offset/side mount brackets, attach PDU to rack as shown.
Rack PDU Manual20
© 2018 Geist
GM1001
Figure 2-8 7" Extension Brackets
7" Extension Brackets (XB-7)
Using the 7 extension brackets, attach PDU to rack as shown.
Figure 2-9 Flush Mount Brackets
Flush Mount Brackets (FM)
Using ush mount brackets, attach PDU to rack as shown.
Chapter 2 - Installation 21
© 2018 Geist
GM1001
Figure 2-10 Adjustable Mount Brackets
Adjustable Mount Brackets (AM)
Using adjustable mount brackets, attach PDU to rack as shown.
Figure 2-11 Panel Mount Brackets
Panel Mount Brackets (PM)
Using panel mount brackets, attach PDU to rack as shown.
Rack PDU Manual22
© 2018 Geist
GM1001
Figure 2-12 23" Conversion Mounting Brackets
23" Conversion Mounting Brackets (23-RM)
Using conversion mounting brackets, attach 19” PDU to 23” rack as shown.
Figure 2-13 Cable Mount Brackets
Cable Mount Bracket (CMB-1)
Attach cable mount bracket to PDU as shown; use tie-wraps to secure cords to bracket.
Chapter 2 - Installation 23
© 2018 Geist
GM1001
Figure 2-14 19" Horizontal/Panel Mount Brackets
19" Horizontal/Panel Mount Brackets (7938)
Using the 19” horizontal/panel mount brackets, attach PDU to rack as shown.
Figure 2-15 Top and Bottom Mounting Clips
Top and Bottom Mounting Clips (9083C & 9084C)
Using the top and bottom mounting clips, attach the PDU to the rack as shown. Please note that
mounting clips are only intended for use with NSV and VSS Series PDUs.
Rack PDU Manual24
© 2018 Geist
GM1001
Chapter 3 - Optional Surge Suppression
Figure 3-1 Surge Suppression LEDs
The SP, SVR, and VSS Series PDUs include a surge suppression circuit that is designed to prevent
voltage surges on the input power line from reaching devices powered by the PDU. The surge
suppression circuit uses Metal Oxide Varistors (MOVs) connected between Line, Neutral, and Ground
wires to prevent voltage surges from damaging connected devices.
Surge Protection Circuit Ratings
Protection Modes Line-Line, Line-Neutral, Neutral-Ground
Maximum Clamping Voltage 340V
Energy Absorption 720 Joules
Green Light Indicator Power On
Red Light Indicator Surge Protection Active
Rack PDU Manual26
© 2018 Geist
GM1001
Service/Tech Support
Service and Maintenance
No service or maintenance is required. Do not attempt to open the PDU or you may void the
warranty. No serviceable parts inside. It is recommended that power be removed from the unit
before installing or removing any equipment.
More Technical Support
http://www.geistglobal.com
Email: support@geistglobal.com
Americas
·1 888 630 4445
Europe and Middle East
·From within the UK 0845 026 3853
·From abroad +44 845 026 3853
Asia
·English +1 888 630 4445 (US number)
·Chinese +86 755 8663 9505
Or contact your distributor.
Thank You For
Purchasing Geist
geistglobal.com

Termékspecifikációk

Márka: Geist
Kategória: elosztó
Modell: BRFA100-10

Szüksége van segítségre?

Ha segítségre van szüksége Geist BRFA100-10, tegyen fel kérdést alább, és más felhasználók válaszolnak Önnek




Útmutatók elosztó Geist

Útmutatók elosztó

Legújabb útmutatók elosztó